Det-Tronics EQ3750ASH EQP Addressable Smoke & Heat (ASH) Module User Manual

Page 4

Advertising
background image

4.2

95-8654

4

pOWER-Up SEQUENCE
Set the ASH Module network address prior to applying

power. Make sure all the necessary connections are made

between the ASH Module and the Controller. At power-up

the “PWR” (Power) LED will illuminate and remain steady.

FAULTS
When a fault condition occurs, a yellow LED on the front

panel of the ASH Module will become active. There are 4

yellow LEDs for different categories of faults.

Module faults
A module fault occurs when a fault is detected within the

ASH Module, such as:
• Low voltage fault

• Memory fault

• Crystal oscillator fault

• Battery fault.

Loop faults
A loop fault is related to the Apollo device’s loop

communication and configuration, such as:
• Open loop

• Shorted loop

• Device missing

• Extra device

• Wrong device

• Multiple devices.

Loop device faults
A loop device fault is related to an individual device on the

loop, and is typically fixed by replacing the faulty device.

Any of the following faults can be categorized as a loop

device fault:
• Integrity check fault

• Device open

• Device short

• Device hardware faults

• Drift warning

• Earth fault.
Ground faults
Ground faults occur when a short or partial short exists

between the loop wiring and earth on the Apollo loop. There

is a local dedicated LED indicator that activates when there

is either a positive or negative ground fault.

CONTROL MESSAGE
The control message manages loop device specific

commands, such as integrity check, LED, relay and sound

control. The control message is transmitted from the

controller every 20 seconds, or immediately when there is

a change in the state of an output channel. A fault will be

annunciated if the control message is not received at the

controller within 2 minutes.

INTEGRITy CHECk
Integrity checks are internal tests that are performed on loop

devices that support the integrity check feature. All Apollo

Discovery detectors and manual call points are equipped with

the integrity check feature. The integrity check may be initiated
and monitored via the ASH Module point display in S

3

.

Table 3—List of Supported Devices

ApOLLO

SpEC SHEET

DET-TRONICS

pART NUMbER

ApOLLO

pART NUMbER

DEvICE NAME

PP2052

000515-501

58000-500

Apollo Ionization Smoke, EU

PP2052

000515-502

58000-600

Apollo Optical Smoke Detector, EU

PP2052

000515-503

58000-400

Apollo Heat Detector, EU

PP2052

000515-504

58000-700

Apollo Multisensor, EU

PP2052

000515-505

58000-300

Apollo Carbon Monoxide Detector, EU

PP2092

000515-509

55000-847

Apollo Input / Output Unit, with Isolator

PP2094

000515-510

55000-852

Apollo Sounder Control Unit

PP2084

000515-511

55000-841

Apollo Switch Monitor Plus

PP2052

000515-512

58100-908

Apollo Manual Call, with Isolator

PP2052

000515-513

58100-951

Apollo Manual Call, with Isolator, IP66

PP2267

000515-515

55000-278

Apollo Sounder, 100dB, Red

PP2267

000515-516

55000-274

Apollo Sounder, 100dB, Red, IP66

PP2156

000515-517

55000-877

Apollo Beacon, Red

PP2267

000515-518

55000-293

Apollo Sounder / Beacon, with Isolator

PP2390

000515-551

58000-550

Apollo Ionization Smoke, NA

PP2390

000515-552

58000-650

Apollo Optical Smoke Detector, NA

PP2390

000515-553

58000-450

Apollo Heat Detector, NA

PP2390

000515-554

58000-750

Apollo Multisensor, NA

39117-468

000515-557

55000-750

Apollo Isolator, NA

PP2390

000515-559

55000-806

Apollo Priority Switch Monitor, NA

PP2390

000515-560

55000-825

Apollo Sounder Control Module, NA

PP2390

000515-561

55000-820

Apollo Input / Output Module, NA

39214-387

000515-562

55000-765*

Apollo Mini Monitor Module, NA or Apollo

Priority Mini Switch Monitor, NA

* The device type depends on the priority switch setting on the device.

NA = North American Approvals

EU = European Approvals