Installation, Configuration – Det-Tronics EQ3750ASH EQP Addressable Smoke & Heat (ASH) Module User Manual

Page 6

Advertising
background image

4.2

95-8654

6

CERTIFICATION —
FM / CSA:

Class

I

, Div. 2, Groups A, B, C, D (T4).

Class

I

, Zone 2, Group

II

C (T4).

ATEX:

II

3 G

Ex nA nC

II

C T4 Gc

DEMKO 10 ATEX 150744X

Tamb = –40°C to +85°C.

Compliance with: EN 60079-0:2012

EN 60079-15:2010.

Special conditions for safe use:

The EQ3750ASH shall be used in an area of no more

than pollution degree 2 per IEC 60664-1, and in an

enclosure with a tool removal cover that complies with

all relevant requirements of EN 60079-15, rated at least

IP54, and be connected to supply circuits where the

rated voltage cannot be exceeded by 40% caused by

transient disturbances.
The EQ3750ASH may only be installed, connected or

removed when the area is known to be non-hazardous.

The maximum surface temperature inside the EQ3750ASH

does not exceed 130°C.

Installation instructions:

For ambient temperatures below –10°C and above

+60°C, use field wiring suitable for both minimum and

maximum ambient temperatures.

The screw terminals are to be tightened with a minimum

torque of 0.5 Nm.

IECEx:

ULD 10.0004X

Ex nA nC

II

C T4 Gc

Tamb = –40°C to +85°C.

Compliance with: IEC 60079-0:2011

IEC 60079-15:2010

The ASH Module can not be used for

applications that fall within the scope

of the CPD directive.

US Coast Guard: As part of the EQP System. Reference

the EQP instruction manual (95-8533)

for more details.

installation

All electrical connections are made to the field wiring

connectors furnished with the module. Refer to Figure 7

for identification of module wiring terminals.

conFiguration

SETTING ASH MODULE NETWORk ADDRESS
One unique network address must be assigned to the

ASH Module. The address is set by the 8 switch DIP

assembly on the module (see Figure 8). The address

is binary coded and is equal to the added value of all

closed switches.

Det-Tronics’ S

3

Safety System Software is used for device

configuration. For complete configuration details, please

refer to the S

3

User’s Guide (95-8560).

LON

S-LOOP

7

8

9

10

11

12

COM 1 SHLD

COM 1 B

COM 1 A

COM 2 SHLD

COM 2 B

COM 2 A

SHLD

B
A

SHLD

B
A

LON FROM
PREVIOUS DEVICE

LON TO
NEXT DEVICE

LOOP IN

LOOP OUT

P2

P3

P1

SHLD

L1 – IN
L2 + IN

L1 – OUT
L2 + OUT

SHLD

SHLD

L1 –
L2 +

SHLD

L1 –
L2 +

DBG**

13

14

15

16

17

18

19

20

21

COM

RX

TX

POWER

1

2

3

4

5

6

SHLD


+

SHLD


+

SHLD

*


+

SHLD

*


+

24 VDC
INPUT VOLTAGE

24 VDC
INPUT VOLTAGE

EQ3750ASH

*

SHIELDS ON POWER WIRES ARE OPTIONAL

UNLESS REQUIRED BY LOCAL CODES.

**

FOR FIELD SERVICE USE ONLY.

B2534

Figure 7—ASH Module wiring Terminals

FM

APPROVED

®