Det-Tronics EQ3750ASH EQP Addressable Smoke & Heat (ASH) Module User Manual

Page 3

Advertising
background image

4.2

95-8654

3

Class X is intended for use in a multi-zone system and

requires that the first isolator on each leg be installed

next to the ASH Module, within the same enclosure. In

addition, an isolator is needed between each zone as

illustrated in Figure 4. Alarm receipt capabilities in the

other zones shall be maintained during a single open,

single ground, wire-to-wire short, or open and ground.

Note

the isolator has an operating temperature range
of +32°F to +100°F (0°C to +38°C). this means
that, for Class X installations, the enclosure
temperature will be rated to +100°F (+38°C) max.

Reference Table 1 for further details on the performance

requirements for SCLs as defined by NFPA 72.

LED INDICATORS
LEDs on the front of the ASH Module are provided for

indicating device status conditions. There are 6 LED

status indicators (Power, ASH Module Fault, Loop Fault,

Loop Device Fault, Ground Fault, and Alarm) located

on the front panel (Figure 5). Refer to Table 2 for a

description of the LED indicators.

MOUNTING
The ASH Module can be DIN Rail or Panel mounted.

ADDRESSAbLE LOOp DEvICES
See Table 3 for a list of all supported Apollo loop devices.

Note

the input and/or output circuits for the Mini
Monitor Module and Priority Mini Switch
Monitor (P/N 55000-765*), Priority Switch
Monitor (P/N 55000-806), Input / output
Module (P/N 55000-820) and Sound Control
Module (P/N 55000-825) must be no longer
than 20 ft (6 m) and must be installed in conduit
or equivalently protected against mechanical
injury.

For additional information and documentation regarding

all Apollo devices, visit www.apollo-fire.co.uk.

A2591

ASH MODULE

NODE 64

NODE 1

...

NODE 63

NODE 3...

NODE 2

ZONE 2

ZONE 1

ZONE 3

. . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

.......

........

ASH MODULE APOLLO LOOP

2-WAY COMMUNICATION

. . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . .

ISOLATOR

ISOLATOR

ISOLATOR

ISOLATOR

ENCLOSURE

Figure 4—Class X Pathway (multi-zone with isolators)

Figure 5—Location of LED Indicators

STATUS

INDICATOR

LEDs

LED

Label

ASH Module Status*

Green

PWR

On when power is present

Yellow

ASH MOD

Fault in the ASH Module

Yellow

LOOP

Loop Fault

Yellow

LOOP DEV

Fault with a device on the loop

Yellow

GND FLT

Ground fault on the Apollo loop

Red

ALARM

An alarm is present

*Reference to “loop” refers to the ASH Module or Apollo device loops.

Table 2—ASH Module Device Status Indicators

Table 1—Performance of Signal Line Circuits (SLCs)

NFpA 72-2010 Class

Class b

Class A

Class X

Alarm

Trouble

ARC

Alarm

Trouble

ARC

Alarm

Trouble

ARC

Condition

1

2

3

4

5

6

7

8

9

Single open

X

X

R

X

R

Single ground

X

R

X

R

X

R

Wire-to-wire short

X

X

X

R

Open and ground

X

X

R

X

R

ARC = Alarm Receipt Capability
R = Required capability
X = Indication required at protected premises