Gateway wiring – Det-Tronics EA2100CG Eagle 2000 Communication Gateway User Manual

Page 24

Advertising
background image

GATEWAY WIRING

Field Wiring Connector

The gateway is furnished with a field wiring connector
backplate that incorporates pressure type screw termi-
nals for connecting the external wiring and a circuit
board edge connector for attaching to the gateway.

The use of a mounting rack is required for mounting the
gateway. The backplate is attached to the back of the
rack to allow easy removal of the gateway without dis-
turbing the wiring. See Figures 22 and 23.

The gateway is designed for installation in a non-haz-
ardous area.

Figure 24 shows the terminal configuration.

Typical Application

Figure 25 illustrates a typical system consisting of a
gateway, communication modules and an OIS. One
communication module is shown with a U8700/U8800
Transmitter.

Figure 26 shows the communication loop and power
wiring for a typical system consisting of a gateway, com-
munication module, network extender and relay module.

CAUTION

The gateway will be damaged if power is inadver-
tently applied to the communication lines. The
gateway is protected against damage caused by
switching polarity of the power lines.

GATEWAY SWITCH SETTINGS

The gateway contains four 8-position DIP switch assem-
blies that are used for:

– Selecting the serial port hardware and software

parameters

– Setting the gateway Modbus address

– Selecting the main gateway

– Setting the gateway address.

Refer to Figure 27 to identify the function of the DIP
switches. Refer to Figure 28 to locate the DIP switch
assemblies on the side of the gateway.

NOTE

Close switch to enable function.

20

1

2

3

4

5

6

7

8

9

18

17

16

15

14

13

12

11

10

CHASSIS GROUND

ALARM

ALARM

CALIBRATE

CALIBRATE

FAULT

FAULT

4 TO 20 MA

RESET

+

EAGLE U8800

SENSOR

A1650

1

2

3

4

5

6

7

8

9

18

17

16

15

14

13

12

11

10

CHASSIS GROUND

COMMUNICATION MODULE

22 AWG SHIELDED TWISTED PAIR

NOTES

1. WIRING TYPE

2.SHIELD CONNECTED AT ONE END ONLY.

GATEWAY/

COM MOD

– +

POWER

SUPPLY

GATEWAY/

COM MOD

ALARM

ALARM

CALIBRATE

CALIBRATE

FAULT

FAULT

+

RESET

+

EAGLE U8700

(JUMPERED FOR NON-ISOLATED CURRENT OUTPUT)

SENSOR

POWER

24 VDC POWER INPUT

NETWORK IN

NETWORK OUT

A

B

A

B

+
+

RELAY COMMON

+

4 TO 20 MA IN

IN 2

COM

IN 1

COM

NC

NO

DIGITAL INPUT 2

DIGITAL INPUT 1

RELAY

DETECTOR POWER

(24 VDC)

24 VDC POWER INPUT

NETWORK IN

NETWORK OUT

A

B

A

B

+
+

RELAY COMMON

+

4 TO 20 MA IN

IN 2

COM

IN 1

COM

NC

NO

DIGITAL INPUT 2

DIGITAL INPUT 1

RELAY

DETECTOR POWER

(24 VDC)

COMMUNICATION MODULE

4 TO 20 MA

POWER

Figure 18—A Typical Application – Communication Module with an Eagle U8700 or U8800 Detector