Application, Features, Specifications – Det-Tronics EA2100CG Eagle 2000 Communication Gateway User Manual

Page 8

Advertising
background image

Multiple Wiring Faults

In the event of multiple wiring faults, the nodes between the
faults will continue to function, but the faults will prevent
them from communicating with the main gateway (Figure 4).
In this example, nodes 1 to 4 communicate using one gate-
way port (path A) and nodes 7 and 8 use the other gateway
port (path B). Nodes 5 and 6 are unable to report to the
gateway because they are isolated by the two wiring faults.

Communication with Relay Modules or
Auxiliary Gateways

It is important to note that data will not “pass through”
the main gateway. This means that when a network
wiring fault condition exists, devices communicating on
one side of the main gateway cannot communicate with
devices on the other side of the gateway (Figure 5). In
this example, devices communicating along path A can-
not communicate with devices using path B.

In the event of a single wiring fault, normal communica-
tion will continue between all communication modules
and the main gateway. However, if the system uses a
relay module (Figure 5) and it is configured to monitor
nodes on the other side of the fault, those devices will be
unable to report to the relay module. For example, only
nodes 4 to 6 (Figure 5) are able to communicate with the
relay module. The relay module cannot receive data
from nodes 1 to 3. In the same way, only nodes 1 to 3
will be able to communicate with the Auxiliary gateway.

IMPORTANT

Since it is impossible to predict where a network
fault might occur or exactly what effect it will have
on actual system operation, it is important to diag-
nose and repair any fault as soon as possible after
it is detected to ensure reliable system operation.

Section II

EA2300CM

Communication Module

APPLICATION

The Eagle Communication Module provides communi-
cation capability for a sensing or control device capable
of generating a 4 to 20 ma signal. In addition to the 4 to
20 ma input, the communication module can also simul-
taneously accept two digital contact inputs. Designed
for use with the Eagle communication gateway, the com-
munication module provides a unique technique for
detecting and isolating opens or shorts in the field
wiring. This fault isolation method allows for communi-
cation integrity in the event of a single break or short on
the communication loop. The communication module
circuitry is mounted inside an explosion-proof metal
housing, which is typically mounted beside the associ-
ated sensing or control device.

The Eagle communication module is compatible with
most Det-Tronics flame detection, gas detection or envi-
ronmental monitoring devices.

FEATURES

• Field addressable

• Fault isolation

• Pass through communication circuitry on power loss

• 4 to 20 ma analog input

• Two digital contact inputs

• Non-volatile memory for logging of alarm and cali-

bration events

• Sealed 5 ampere SPDT relay

• 2 adjustable alarm setpoints

• 10 bit signal resolution

• EMI hardened

• Screw terminal connectors

SPECIFICATIONS

INPUT VOLTAGE—

18 to 32 vdc.

INPUTS—

4 to 20 ma analog signal, with an input impedance of
200 ohms in series with a protection diode. Two digital
inputs (for switch or relay contacts). One is dedicated
to either detector calibration or detector fault indication
(refer to the System Configuration Matrix, form 95-8453).
The other is available for general use, with either a nor-
mal or inverted input.

4

A1646

MAIN

GATEWAY

NODE 1

NODE 8

NODE 3

NODE 6

NODE 2

NODE 7

NODE 4

NODE 5

PATH A

PATH B

WIRING FAULT

Figure 4—Communication with Multiple Wiring Faults on the Network

A1647

MAIN

GATEWAY

NODE 1

NODE 6

NODE 2

RELAY

MODULE

NODE 5

NODE 3

NODE 4

PATH A

PATH B

AUXILIARY

GATEWAY

WIRING FAULT

Figure 5—Network Wiring Fault Affects Communication

with Relay Module and Auxiliary Gateway

Advertising