S5 – Hardware Serial Port Configuration

1 and 2

Channel 0 not used. Leave switches open.

3

Close if RS-232 is used.

4

Close if RS-422 is used. (Macintosh uses
RS-422.)

5 and 6

Channel 0 not used. Leave switches open.

7 and 8

Close switches.

S6 – Software Serial Port Configuration

1, 2, and 3 Determine the desired baud rate, then refer

to Table 6 for the proper switch settings.
(19,200 is recommended.)

4

Leave switch open (no parity).

5

Leave switch open (odd parity).

6

Leave switch open (1 stop bit).

7

Close switch (8 data bits).

8

Leave switch open.

S7 – Modbus Address

Set switches to match Modbus slave address. Setting
must be different for each gateway, unless redundant
gateways are used. (Backup gateway must have same
address as main gateway.) “0” is not a valid address.

S8 – Network Configuration

1 and 2

Set gateway address switches according to
Table 7.

3 to 5

Not used. Leave open.

6

Close for non-latching gateway relays.

7

Close switch if gateway is to function as a
backup gateway. Switch must be open for
main or auxiliary gateway.

8

Close for main gateway, open for all other
gateways.

21

95-8424

1

2

3

4

5

6

7

8

9

1

2

3

4

5

6

7

8

9

COMMUNICATION MODULE/DCU

18

17

16

15

14

13

12

11

10

RED

BLACK

GREEN

SENSOR

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

422 TXD

+

422 TXD

CHASSIS GND

+

422 RXD

+

422 RXD

EXT RESET

COM

232 TXD

232 RXD

COM

A

B

A

B

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

CHASSIS GND

GATEWAY

K1

K2

K3

K4

FAULT

+

24 VDC POWER INPUT

NETWORK IN

NETWORK OUT

A

B

A

B

+
+

RELAY COMMON

+

4 TO 20 MA IN

IN 2

COM

IN 1

COM

NC

NO

DIGITAL INPUT 2

DIGITAL INPUT 1

RELAY

DETECTOR POWER

(24 VDC)

COMMUNICATION MODULE/DCU

18

17

16

15

14

13

12

11

10

24 VDC POWER INPUT

NETWORK IN

NETWORK OUT

+

4 TO 20 MA IN

IN 2

COM

IN 1

COM

NC

NO

DIGITAL INPUT 2

DIGITAL INPUT 1

RELAY

24 VDC

NET 0

NET 1

24 VDC

A1588

22 AWG SHIELDED TWISTED PAIR

WIRING TYPE

RED

BLACK

GREEN

SENSOR

DETECTOR POWER

(24 VDC)

CHASSIS

CHASSIS

A

B

A

B

+
+

RELAY COMMON

Figure 19—A Typical Application – Communication Modules or DCUs with Toxic Gas Sensors

Advertising