Det-Tronics EA2100CG Eagle 2000 Communication Gateway User Manual

Page 33

Advertising
background image

29

95-8424

CALIBRATION ALGORITHM A
(Type Codes 1, 2, 3, 4) for Gas Detectors

Normal Calibration

1.

Activate the reed switch or input 1 on the communi-
cation module (See Figure 29). The red LED blinks
at a 2 Hz rate while the reed switch or input 1 is
closed.

2.

After the reed switch has been closed for 3 sec-
onds, the calibrate LED on the communication mod-
ule flashes at a 1 Hz rate, indicating that it is ready
for the zero input. The calibrate bit in the communi-
cation module status word is set.

3.

Apply the zero input (4 ma).

4.

Activate the reed switch or input 1 on the communi-
cation module. The red LED will blink at a 2 Hz rate
for 3 seconds while the reed switch or input 1 is
closed.

5.

After the reed switch or input 1 has been closed for
3 seconds, the communication module records the
uncalibrated value in the calibration log and cali-
brates the zero value. The calibrate LED goes on
steady.

6.

Apply the calibration gas.

7.

The calibrate LED blinks at a 1 Hz rate when the
input increases.

8.

Activate the reed switch or input 1 on the communi-
cation module. The red LED blinks at a 2 Hz rate
while the reed switch or input 1 is closed.

9.

The communication module records the uncalibrat-
ed value in the calibration log and calibrates the
span value after the reed switch or input 1 is on for
3 seconds.

10. The calibrate LED goes on steady.

11. Remove the span gas and return the analog input to

normal.

12. Activate the reed switch or input 1 on the communi-

cation module. The red LED blinks at a 2 Hz rate for
3 seconds while the reed switch or input 1 is closed.

13. The calibration is complete. The calibrate LED turns

off and the calibrate bit in the status word is reset.

If the calibration is not completed within 12 minutes, the
previous calibration values are restored and the calibra-
tion is logged as aborted. The calibrate LED flashes at
a 4 Hz rate, the calibrate bit in the status word is reset
and the calibration fault bit is set.

Calibration After Sensor Replacement

1.

Open the junction box cover and press the sensor
replacement switch.

2.

The calibrate LED on the communication module
flashes at a 1 Hz rate, indicating it is ready for the
zero input. The calibrate bit in the status word is
set.

3.

Replace the sensor and apply the zero input (4 ma).

4.

Activate the reed switch or input 1 on the communi-
cation module. The red LED blinks at a 2 Hz rate for
3 seconds while the reed switch or input 1 is closed.

5.

The communication module records the uncalibrat-
ed value in position one of the calibration log and
calibrates the zero value. The calibrate LED goes
on steady.

6.

Apply the calibration gas.

7.

The calibrate LED blinks at a 1 Hz rate when the
input increases.

8.

Activate the reed switch or input 1 on the communi-
cation module. The red LED blinks at a 2 Hz rate for
3 seconds while the reed switch or input 1 is closed.

9.

The communication module records the uncalibrat-
ed value in the first register of the calibration log
and calibrates the span value.

10. The calibrate LED goes on steady.

11. Remove the span gas and return the analog input to

normal.

12. Activate the reed switch or input 1 on the communi-

cation module. The red LED blinks at a 2 Hz rate for
3 seconds while the reed switch or input 1 is closed.

13. The calibration is complete. The calibrate LED

turns off and the calibrate bit in the status word is
reset.

Pressing the sensor replacement switch aborts the cali-
bration and starts over. Resetting the communication
module will abort sensor replacement.

3 SEC

3 SEC

3 SEC

3 SEC

3 SEC

3 SEC

3 SEC

3 SEC

3 SEC

ACCEPT ZERO

ACCEPT SPAN

ACCEPT ZERO

ACCEPT ZERO

ACCEPT SPAN

FRESH AIR

REMOVE GAS

SPAN GAS

ZERO GAS

3O SEC MIN

3O SEC MIN

3O SEC MIN

RECORD SPAN

TRENDING SPAN

REED SWITCH

ANALOG IN

LED

REED SWITCH

ANALOG IN

LED

REED SWITCH

ANALOG IN

LED

U8800 INPUT

ANALOG IN

LED

IN ONE

A1555

ACCEPT ZERO

ACCEPT SPAN

3 SEC

3 SEC

OLD SPAN

CALIBRATED SPAN

1

SEC

UNCONTROLLED ANALOG SIGNAL

UNCONTROLLED ANALOG SIGNAL

UNCONTROLLED ANALOG SIGNAL

UNCONTROLLED ANALOG SIGNAL

A1555

A1555

A1555

3O SEC MIN

3 SEC

3 SEC

3 SEC

ACCEPT ZERO

ZERO

IN ONE

ANALOG IN

LED

A1555

UNCONTROLLED ANALOG SIGNAL

Figure 29—Calibration Algorithms "A" and "F"