INSTALLATION CHECKLIST

The following checklist is provided as a means of dou-
ble checking the system to be sure that all phases of
system installation are complete and have been per-
formed correctly.

1.

Junction boxes are mounted securely and detectors
are pointing in the proper direction.

2.

All cable shields are properly grounded.

3.

All junction box covers are tightly installed.

4.

Explosion-proof conduit seals or watertight glands
have been installed at all junction box entries.

5.

Sensor and communication network wiring is correct.

6.

Power wiring is installed and power source is opera-
tional.

7.

External loads are properly connected.

8.

DIP switches on the communication modules are set
correctly. Record this information for future reference.

9.

Gateway switches are set as desired. Record this
information for future reference.

10. Gateway is properly installed in the mounting rack.

11. Proper ventilation is provided (if needed) to prevent

equipment over-heating.

Proceed to System Startup.

27

95-8424

PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED)
BAUD RATE BIT 2 (MSB)
BAUD RATE BIT 1
BAUD RATE BIT 0 (LSB)

PARITY TYPE (OFF = ODD, ON = EVEN)

NUMBER OF STOP BITS (OFF = 1, ON = 2)

RS-422/RS-485 (OFF = RS-422, ON = RS-485)
NUMBER OF DATA BITS (OFF = 7, ON = 8)

1

2

3

4

5

6

7

8

S6 SOFTWARE SERIAL PORT CONFIGURATIONS (CHANNEL 1 ONLY)

0 = 1200
1 = 2400
2 = 9600

3 = 19200
4 = 57600
5 = 38400

6 = 300
7 = 4800

A1554

CHANNEL 1 RS-422 RECEIVER ENABLE
CHANNEL 1 RS-232 RECEIVER ENABLE
CHANNEL 0 RS-422 RECEIVER ENABLE
CHANNEL 0 RS-232 RECEIVER ENABLE

CHANNEL 0 RS-422 TRANSMITTER TERMINATION

CHANNEL 0 RS-422 RECEIVER TERMINATION

CHANNEL 1 RS-422 RECEIVER TERMINATION
CHANNEL 1 RS-422 TRANSMITTER TERMINATION

1

2

3

4

5

6

7

8

S5 HARDWARE SERIAL PORT CONFIGURATIONS

MODBUS ADDRESS BIT 3
MODBUS ADDRESS BIT 2
MODBUS ADDRESS BIT 1
MODBUS ADDRESS BIT 0 (LSB)

MODBUS ADDRESS BIT 4

MODBUS ADDRESS BIT 5

MODBUS ADDRESS BIT 7 (MSB)
MODBUS ADDRESS BIT 6

1

2

3

4

5

6

7

8

S7 MODBUS ADDRESS

UNDEFINED
UNDEFINED
GATEWAY ADDRESS BIT 1 (MSB)
GATEWAY ADDRESS BIT 0 (LSB)

UNDEFINED

NON-LATCHING GATEWAY RELAYS

MAIN/AUXILIARY GATEWAY (OFF = AUX, ON = MAIN)
BACKUP GATEWAY

1

2

3

4

5

6

7

8

S8 LON CONFIGURATION

S8

S7

S6

S5

A1546

BAUD RATE

SWITCH POSITIONS

1

2

3

1200

Op

Op

Op

2400

Cl

Op

Op

9600

Op

Cl

Op

19,200

Cl

Cl

Op

57,600

Op

Op

Cl

38,400

Cl

Op

Cl

300

Op

Cl

Cl

4800

Cl

Cl

Cl

GATEWAY FUNCTION

SWITCH POSITIONS

1

2

Main Gateway

Op

Op

1st Aux. Gateway

Cl

Op

2nd Aux. Gateway

Op

Cl

3rd Aux. Gateway

Cl

Cl

Figure 27—Gateway DIP Switch Assignments

Figure 28—Gateway DIP Switch Location

Op = Open
Cl = Closed

Table 6—Baud Rate Selection – Switches S6-1, S6-2, S6-3

Table 7—Gateway Address – Switches S8-1, S8-2

Op = Open
Cl = Closed