IV. OPERATING INSTRUCTIONS

A. Normal Operation

1. Handheld Controller

Power On/Off – Press and hold the AUX button to wake up or power down the Handheld Controller.

 Sleep ModeThe Handheld Controller will enter sleep mode after five minutes of inactivity. The

blue power LED will blink once every five seconds while in sleep mode. Pressing any button will
exit sleep mode and return the controller to normal operation.

 Hibernate Mode – Within 10 minutes of inactivity in sleep mode, the handheld will then enter

hibernate mode. The handheld is inoperable and all LEDs will be turned off when in hibernate
mode. Pressing the AUX button will exit hibernate mode and return the controller to normal
operation.

Directional buttons – Right, Left, Up, Down, Fog, and Straight Stream – Move the monitor and nozzle
in the appropriate direction. The amber ‘Fog-Stream,’ ‘Right-Left,’ and ‘Up-down’ LEDs on the
monitor control box will light up as long as the monitor is moving in the respective directions.

Oscillate button
- Used to set the limits and initiate oscillation. For a two axis oscillation:

 Move monitor to the upper right position of the desired oscillation range.
 Press and release the OSCILLATE button.

 Move monitor to the lower left position of the desired oscillation range.

 Press and release the OSCILLATE button.
 The monitor will immediately start oscillating in both the horizontal and vertical directions.

 In order to oscillate either horizontally only or vertically only, move the monitor only on the axis

of desired movement (horizontal or vertical).

o

When oscillating in one axis only, movement in the other axis is allowed without cancelling

the oscillation.

 Pressing the OSCILLATE button or moving the monitor in a direction the oscillate command was

programmed for will cancel the oscillation command.

 If there is no monitor movement for 30 seconds while setting up the oscillation limits, the monitor

will automatically exit oscillate setup.

Stow – Press and hold OSCILLATE and FOG simultaneously for TWO (2) or more seconds, the unit
will auto-stow.

Caution: Water should NOT be flowing while stowing the monitor.

2. Docking Station

A docking station will be utilized if the handheld input controller is used. The handheld transmitter uses
one 3.7V lithium ion battery. The docking station provides a means of charging the battery. To charge
the handheld, simply place it in the docking station and slide the top portion of the docking station
downward. This will secure the handheld as well as charge the battery.