Status indications, 8 status indications – ElmoMC SimplIQ Analog Servo Amplifiers-Violin Installation User Manual

Page 21

Advertising
background image

Violin Installation Guide

Servo Control Operation

MAN-VIOIG (Ver. 2.3)

4-5

4.8 Status

Indications

The following table lists the Violin amplifier status indications.


Function

Latch
Option


AOK


SO1


SO2


SO3

1 Amplifier

OK

(AOK)

N/A

Low

Open collector Open collector Open collector

2

External disable No

Low

Low

Open collector Low

3

Current limit

No

Low

Open collector Open collector Low

4

Short

Yes

Open collector Low

Open collector Low

5 Over

temperature

Yes

Open collector Open collector Low

Low

6 Internal

supplies

protection

No

Open

collector

Low Low Open

collector

7

Under voltage

No

Open collector Low

Open collector Open collector

8

Over voltage

No

Open collector Open collector Low

Open collector

9

Shunt*

No

Low

Open collector Low

Open collector

10 Power Up Reset No

Open collector Open collector Open collector Open collector

* This indication can be used as a digital input for activating an external shunt regulator.

Table 4-3: Violin Status Indications

Notes:

Without latch mode:

The status indications are reset when the fault disappears.

With latch mode:

The Short and Over Temperature Failure status indications are reset when the
enable signal is temporarily removed from the enable input.

Multiple faults:

Only the reading of the first fault is reliable. Additional faults add on to the
status outputs and the indication is therefore meaningless.