—15—

PERFORMANCE DATA (cont)

STANDARD INDOOR ECM MOTOR

COOLING CAPACITIES (cont)

574B048 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air—CFM/BF

1260/0.06

1400/0.06

1600/0.08

Evaporator Air — Ewb (F)

62

63*

67

72

62

63*

67

72

62

63*

67

72

75

TC
SHC
kW

45.0

45.8

49.6

54.7

46.7

47.3

51.2

56.3

48.1

48.7

52.5

57.8

39.3

32.0

33.4

27.2

42.6

34.3

35.8

28.9

45.8

36.8

38.4

30.6

3.4

3.4

3.4

3.4

3.4

3.4

3.4

3.5

3.4

3.4

3.4

3.5

85

TC
SHC
kW

42.8

43.6

47.2

52.1

44.3

44.9

48.6

53.5

45.6

46.1

49.9

54.8

38.2

30.9

32.3

26.2

41.3

33.2

34.7

27.7

44.3

35.5

37.3

29.4

3.7

3.7

3.8

3.8

3.7

3.7

3.8

3.8

3.8

3.8

3.8

3.8

95

TC
SHC
kW

40.6

41.3

44.7

49.4

41.8

42.4

46.0

50.7

44.2

43.7

47.0

51.8

36.9

29.8

31.2

25.2

39.9

32.0

33.6

26.7

43.0

34.6

36.1

28.3

4.1

4.1

4.2

4.2

4.1

4.1

4.2

4.2

4.2

4.1

4.2

4.2

105

TC
SHC
kW

38.2

38.9

42.1

46.4

39.6

39.8

43.1

47.6

41.5

40.8

44.0

48.5

35.7

28.7

30.1

24.0

38.3

30.7

32.3

25.5

40.0

33.2

34.8

27.0

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.7

4.6

4.6

4.6

4.7

115

TC
SHC
kW

35.7

36.3

39.3

43.3

38.2

37.1

40.1

44.2

38.7

37.9

40.8

45.0

34.4

27.5

28.9

22.9

35.7

29.5

31.0

24.3

38.2

31.8

33.5

25.8

5.0

5.0

5.1

5.1

5.1

5.0

5.1

5.1

5.1

5.1

5.1

5.1

125

TC
SHC
kW

33.4

33.4

36.2

39.4

34.6

34.1

36.9

40.5

36.1

34.8

37.5

41.2

32.1

26.2

27.6

21.5

33.8

28.2

29.7

22.9

35.6

30.2

31.9

24.4

5.6

5.6

5.6

5.7

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

574B060 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air — CFM/BF

1500/0.004

1750/0.007

2000/0.01

Evaporator Air — Ewb (F)

62

63*

67

72

62

63*

67

72

62

63*

67

72

75

TC
SHC
kW

57.2

58.2

62.4

68.1

58.8

59.7

64.0

69.8

60.0

60.8

64.9

70.8

49.4

47.9

41.6

33.8

53.6

51.8

44.5

35.4

57.6

55.4

47.1

36.8

4.1

4.1

4.2

4.2

4.2

4.3

4.3

4.4

4.4

4.4

4.5

4.6

85

TC
SHC
kW

54.7

55.6

59.7

65.2

56.2

57.0

61.1

66.6

57.4

58.1

61.9

67.4

48.2

46.7

40.4

32.6

52.4

50.5

43.2

34.2

56.3

54.2

45.8

35.6

4.5

4.5

4.6

4.7

4.7

4.7

4.8

4.9

4.8

4.9

5.0

5.0

95

TC
SHC
kW

52.2

53.0

56.9

62.0

53.5

54.3

58.0

63.2

55.0

55.3

58.7

64.1

47.0

45.4

39.2

31.4

51.1

49.2

41.9

32.9

55.0

52.9

44.5

34.4

5.0

5.0

5.1

5.2

5.1

5.2

5.3

5.3

5.2

5.3

5.5

5.5

105

TC
SHC
kW

49.4

50.2

53.8

58.7

50.7

51.4

54.8

59.6

52.5

52.4

55.4

60.2

45.7

44.1

37.9

30.1

49.8

47.9

40.6

31.6

52.5

51.6

43.2

33.0

5.5

5.6

5.6

5.7

5.7

5.7

5.8

5.9

5.8

5.8

6.0

6.1

115

TC
SHC
kW

46.5

47.2

50.5

55.0

48.1

48.3

51.3

56.8

49.7

49.7

51.8

57.0

44.3

42.7

36.4

28.7

48.1

46.6

39.2

30.6

49.7

49.7

41.8

31.7

6.1

6.2

6.2

6.3

6.2

6.3

6.4

6.4

6.4

6.4

6.6

6.6

125

TC
SHC
kW

43.3

43.9

46.7

52.2

45.2

45.1

47.4

52.5

46.4

46.4

47.9

52.2

42.8

41.2

34.9

27.8

45.2

45.1

37.6

28.9

46.4

46.4

40.2

29.7

6.7

6.8

6.8

6.8

6.8

6.9

7.0

7.0

7.0

7.0

7.2

7.2

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

Total Unit Power Input

SHC

Sensible Heat Capacity (1000 Btuh)

TC

Cooling Capacity (1000 Btuh)

ECM

Electronic Computated Motor

*

TVA Conditions (75°F entering dry bulb)

NOTES:
1. Ratings are net; they account for the effects

of the evaporator-fan motor power and heat.

2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

؊

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

؊

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

4. The SHC is based on 80°F edb temperature of air entering evaporator

coil. Below 80°F edb, subtract (Corr Factor x CFM) from SHC above
80°F edb, add (Corr Factor x CFM) to SHC Correction Factor = 1.10 x
(1 – BF) x (edb – 80)