574B COOLING DRY COIL ECM AIRFLOW—SMALL CABINET

574B COOLING DRY COIL ECM AIRFLOW—LARGE CABINET

574B HEATING ECM AIRFLOW—SMALL CABINET

574B HEATING ECM AIRFLOW—LARGE CABINET

UNIT

SIZE

CFM ADJUST

PIN SELECT

LO PIN

NOM PIN

HI PIN

EXTERNAL STATIC

PRESSURE RANGE

0.0–0.39

0.4–0.69

0.7–1.0

0.0–0.39

0.4–0.69

0.7–1.0

0.0–0.39

0.4–0.69

0.7–1.0

024

COOLING

745

675

835

750

690

940

880

815

COOLING

DEHUMIDIFY

675

625

675

650

600

755

730

705

030

COOLING

940

860

785

1020

965

895

1185

1100

1010

COOLING

DEHUMIDIFY

820

785

735

820

800

770

955

920

880

036

COOLING

1025

935

1145

1085

1005

1320

1260

1180

COOLING

DEHUMIDIFY

925

885

925

900

870

1060

1040

1010

UNIT

SIZE

CFM ADJUST

PIN SELECT

LO PIN

NOM PIN

HI PIN

EXTERNAL STATIC

PRESSURE RANGE

0.1–1.0

0.1–1.0

0.1–1.0

042

COOLING

1035

1095

1280

COOLING

DEHUMIDIFY

880

880

1025

048

COOLING

1150

1285

1500

COOLING

DEHUMIDIFY

1025

1025

1200

060

COOLING

1480

1630

1920

COOLING

DEHUMIDIFY

1305

1305

1535

EASY SELECT™

BOARD SETTING (CFM)

700

800

1100

1250

UNIT

SIZE

EXTERNAL STATIC

PRESSURE

0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0

GAS HEAT SIZE

024

040

855

770

710

030

040

880

840

805

060

1030

970

910

036

060

1035

995

955

090

1170

1110

1025

EASY SELECT™

BOARD SETTING (CFM)

1000

1250

1600

1750

1800

UNIT

SIZE

EXTERNAL STATIC

PRESSURE

0.0–1.0

0.0–1.0

0.0–1.0

0.0–1.0

0.0–1.0

GAS HEAT SIZE

042

060

1000

090

1250

048

090

1250

115

1600

130

1750

060

090

1250

115

1600

130

1800

Advertising