Electrical data 574b (standard) electrical data – Bryant 574B User Manual

Page 21

Advertising
background image

—21—

C99024

ELECTRICAL DATA

574B (STANDARD) ELECTRICAL DATA

UNIT

SIZE

574B

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR FAN

MOTOR

INDOOR FAN

MOTOR

POWER SUPPLY

Min

Max

RLA

LRA

FLA

FLA

MCA

MAX FUSE

OR BKR

024

208/230–1–60

187

253

13.5

61.0

0.8

4.3

22.0/22.0

30/30

030

208/230–1–60

187

253

16.9

73.0

0.8

4.3

25.0/25.0

30/30

036

208/230–1–60

187

253

15.9

83.0

0.8

6.8

28.7/28.7

35/35

208/230–3–60

187

253

12.2

77.0

0.8

6.8

22.9/22.9

30/30

042

208/230–1–60

187

253

22.4

105.0

0.8

6.8

35.6/35.6

45/45

208/230–3–60

187

253

15.4

88.0

0.8

6.8

26.9/26.9

35/35

048

208/230–1–60

187

253

21.3

109.0

1.6

6.8

35.0/35.0

45/45

208/230–3–60

187

253

14.7

91.0

1.6

6.8

26.8/26.8

35/35

060

208/230–1–60

187

253

27.0

145.0

1.6

9.1

44.5/44.5

60/60

208/230–3–60

187

253

18.1

123.0

1.6

9.1

33.3/33.3

40/40

452 = 5 v

457 = 7 v
455 = 2 v

LEGEND

FLA

— Full Load Amps

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
RLA

— Rated Load Amps

NOTES:
1. In compliance with NEC (National Electrical Code) requirements

for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.

2. Minimum wire size is based on 60 C copper wire. If other than

60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.

% Voltage imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457
(BC) 464
(AC) 457

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

®

*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.

If power distribution voltage to unit varies from rated heater voltage,
heater KW will vary accordingly.