Physical data (cont) – Bryant 574B User Manual

Page 6

Advertising
background image

—6—

PHYSICAL DATA (cont)

Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air-

flow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure
drop for non-standard filters must not exceed 0.08 in. wg.

**

Based on altitude of 0 to 2000 ft.

UNIT SIZE 574B

048090

048115

048130

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

5

5

5

OPERATING WEIGHT (lb)

463

463

463

499

499

499

COMPRESSORS

Scroll

Quantity

1

REFRIGERANT (R-410A)

Quantity (lb)

11.25

11.25

11.25

13.5

13.5

13.5

REFRIGERANT METERING DEVICE

Indoor

TXV

CONDENSER COIL

Rows—Fins/in.

2/21

2/21

2/21

2/21

2/21

2/21

Face Area (sq ft)

17.4

17.4

17.4

19.3

19.3

19.3

CONDENSER FAN

Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

EVAPORATOR COIL

Rows—fins/in.
Face Area (sq ft)

4/15

4.7

4/15

4.7

4/15

4.7

4/17

5.7

4/17

5.7

4/17

5.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)

1400

11 x 10

3/4

1400

11 x 10

3/4

1400

11 x 10

3/4

1750

11 x 10

1.0

1750

11 x 10

1.0

1750

11 x 10

1.0

FURNACE SECTION**

Burner Orifice No. (Qty…Drill Size)

Natural Gas

Burner Orifice No. (Qty…Drill Size)

Propane Gas

3…38

3…46

3…33

3…42

3…31

3…41

3…38

3…46

3…33

3…42

3…31

3…41

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto.)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto.)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway†

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

Advertising