16. TEST INC

Set the test increment units to percent or hexadecimal.

The level for the dimmer test (DIM TEST) menu can be displayed as a percentage or

hexadecimal value.

PERCENT

Press EXECUTE to toggle test increments from PERCENT to HEX VAL.

HEX VAL

Press EXECUTE to toggle test increments from HEX VAL to PERCENT.

Any change in the configuration is automatically saved.

17. SCENEMOD

Enable or disable scene mode.

Enabling scene mode puts the system in scene mode. With scene mode enabled

the selected scene will always be activated when DMX is not being received (DMX

automatically takes precedence over scene mode). The selected scene can be

changed in the SCENESET menu. Scene mode enables the use of the auxiliary

inputs when they are configured to activate a scene. A contact closure sensed on the

over-temperature, fire alarm or security alarm inputs automatically takes precedence

over scene mode.

ENABLED

Press EXECUTE to toggle scene mode from ENABLED to DISABLED.

DISABLED

Press EXECUTE to toggle scene mode from DISABLED to ENABLED.

Any change in the configuration is automatically saved.

18. AUX TEST

Test the auxiliary dry-contact inputs.

Both of the auxiliary dry-contact inputs can be tested to ensure they are operating

properly. The auxiliary inputs are simply a maintained normally-open switch

connection between common and the auxiliary input. When there is a connection

between common and the auxiliary input, the auxiliary input is activated.

Press EXECUTE to enter the menu.

1: 2:

Displays auxiliary input 1 (1:) and auxiliary input 2 (2:).

1:* 2:

The asterisk (*) indicates if auxiliary input 1 is activated.

1: 2:*

The asterisk (*) indicates if auxiliary input 2 is activated.

Press ESCAPE to exit the menu.

19. AUX1MODE

Set the auxiliary input 1 mode to activate a selected scene or load shed.

The auxiliary dry-contact input can be set to activate 1 of the 6 backup scenes, or set

for load shed mode (LS). When the auxiliary input is configured to activate a scene,

scene mode (SCENEMOD) must be enabled for the selected scene to be activated.

Refer to menu item SCENEMOD on page XX for further details. When the auxiliary

input is configured for load shed mode, dimmers channels selected within the load

shed (LOADSHED) menu are disabled (turned off). Refer to menu item LOADSHED

on page XX for further details.

When both auxiliary inputs are configured to activate a scene, the last action takes

precedence, meaning the last contact sensed activates the selected preset.

SCENE:01

Displays the mode setting for the auxiliary input.

SCENE>01

Press EXECUTE to enter the menu and edit the mode.

SCENE>06

Press MENU ( ) to select the desired scene to activate from 01 to 06.

SCENE>LS

Press MENU ( ) to set the auxiliary input to load shed mode (LS).

Press ESCAPE to exit the menu and save the desired mode.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 2 minutes of inactivity and save.