3 installation – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual

Page 19

Advertising
background image

02.08 [IGBT Power Converter 70/100A]

19

3 Installation

that flows at max. load voltage (e.g. 140V) through the load resistor

Power loss = 90(A) x power loss factor

Power loss = 90(A) x 8.5 = 765W

Example of the
SIC heating
elements

SIC heating elements

SIC heating element data: new: 70V/90A, old 140V/45A; P = 6300W

h Determine the maximum load voltage actually (e.g. 70V) of the new SIC

heating element and find the point intersecting with the curve for the
voltage supply in the power section. The Y axis shows the attendant power
loss factor of, e.g., 6.8.

The power loss (W) is obtained by multiplying this power loss factor by the
load current (e.g. 90A)
that flows at max. load voltage (e.g. 70V) through the new SIC heating element

Power loss = 90(A) x power loss factor

Power loss = 90(A) x 6.8 = 612W

Wall
fixing

h Use 4 hexagonal M6 bolts (at least quality 8.8) to fix the converter vertically

on a heat-resistant switch cabinet back panel.

IPC type: 709050/92-12-400-150-100/252
Load voltage = 150V
Load current = 100A
Voltage supply to the power section = 400V
P control, P = 6300W

H

The temperature of the air drawn in through the ventilation grille
must not exceed 35° C. Ensure that the inlet air for the built-in
ventilators can be taken in from below and escape at the top
without obstruction!