4 electrical connection – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual

Page 29

Advertising
background image

02.08 [IGBT Power Converter 70/100A]

29

4 Electrical connection

Choke connection

1C

C

Load connection

1D -

D +

Connection for

terminal screw X102

Detail

Current input
(differential input)

1-
2+

Voltage input
(referred to ground)

3 ground
4+

External manual adjustment

Potentiometer 5 k

3 Start (ground)
4 slider
5 end (+10V)

Firing pulse inhibit
(inhibit input) I

K

approx. 1mA

(break or make contact)

6 ground
7+

Output level 0 to 10V (U

2

, P, I

2

)

I

max

approx. 2mA

10+
6 ground

Resistance output 0 to 5 V (R)
I

max

approx. 2mA

8 +
6 ground

8

6

+

Connection for

Screw terminal X103

Detail

Load fault output with relay
contact rating 230V AC/3A
resistive load
relay drops out at fault

1 make contact
2 break contact
3 common

Load fault output with
optocoupler Ic

max

= 2mA

U

CEO max

= 32 V

3 collector
1 emitter

Advertising