02.08 [IGBT Power Converter 70/100A]

43

5 Settings

5.12 Safety cut-out in the power section

If there is a fault in the choke or the control electronics, the output voltage is
switched off between terminals D and 1D.

This state is indicated by the „IGBT“ LED, and the fault signal relay drops out.
This safety cut-out remains activated even when the fault has been remedied.
It can only be reset by disconnecting the voltage supply.

h Switch the device off briefly, and then on again

5.13 Adjusting the output level signal (output adjust U

2

, P , I

2

)

In the factory settings, the output level signal corresponds to the I

2

signal at

the output of the converter. It is thus proportional to the power in the load
(R=constant).

However, setting P or U

2

instead of the I

2

signals is also possible

v Chapter 5.2 „Setting switches S101, S103, S104, S105, S106 and X106“

Output adjust
U

2

, P, I

2

The output level signal provides a voltage in the range of 0 to 10V
(corresponding to 0 to 100% of the variable being measured). The trimmer

„output adjust U

2

, P , I

2

“ on the front panel can be used to set the required

end value:

A

However, terminals D and 1D may still carry dangerous voltage from
the supply. They are not electrically isolated from the supply!

Power level output

Internal switches

S4

S5

S6

U

2

1

0

0

P

0

1

0

I

2

0

0

1

Action

Response

Turn „output adjust U

2

, P , I

2

“ trimmer

clockwise

End value increases

Turn „output adjust U

2

, P , I

2

“ trimmer

counter-clockwise

End value reduces