7 Troubleshooting

IPC does not produce
full power, although
setpoint is set to 100%

- Switch positions for control input S 101/8

and 9 or S104 set incorrectly

v Chapter 5.5 „Control

inputs“

- Control input (max. Power adjust) is not

turned clockwise to the stop

h Check adjustment

v Chapter 5.8.3

„Control input
adjustment (max.
Power adjust)“

- Current limiting active (when the red

„current limit“ LED is lit)

h Turn the „max. current adjust“ trimmer

clockwise

v Chapter 5.10

„Setting the current
limit (max. current
adjust)“

- Resistance limiting (R-control) active

h Check switch S 101/10

v Chapter 5.2 „Setting

switches S101,
S103, S104, S105,
S106 and X106“

h Check switch S 103
h Check switch S 101/7

IPC is producing power,
although no setpoint
value is set

- Check switches S 101/ 8 and 9 or S104

for control input

v Chapter 5.5 „Control

inputs“

- Base load setting (max. Power adjust) is

not turned counter-clockwise to the stop

h Check switch S 101/11

v Chapter 5.9 „Setting

the base load (min.
Power adjust)“

What is happening?

Cause / Remedy