2 alarm configuration, Alarm configuration, Chapter 17.2 "alarm configuration – JUMO 706581 LOGOSCREEN nt Operating Manual User Manual

Page 127: 17 configuration - external binary inputs

Advertising
background image

127

17 Configuration - External Binary Inputs

17.2 Alarm Configuration

Overview

Status

Status activates alarm monitoring.

Alarm type

The alarm type determines whether the activating/inactivating of an input is to
be evaluated as a genuine alarm or only as an event.

Alarm active on

Determines whether the alarm is present with an active or inactive input.

Alarm text

Text that is entered in the event or alarm list and displayed in the “status & title
bar”, with the alarm type “Alarm”.

Alarm delay

This parameter delays the reporting of an alarm. If the alarm is no longer
present after the alarm delay time has elapsed, it will not be triggered.

On

Alarm monitoring is active.

Event

The alarm text is entered in the event list only.

Alarm

The alarm text is entered in the alarm list and the event
list. In addition, the alarm text appears in the “status &
title bar”, and the alarm bell is shown in red.

Alarm text

Alarm bell

High (1)

Alarm with active input.

Low (0)

Alarm with inactive input.