MES1B for RS-485 two-wire operation, the CP1 parameter must be set for
RS485 Enable to ensure Send Data Control is implemented.

No configuration is required in this section for MES1A converters.

To configure RS485 Enable in the Modem/Configurable Pin Settings
section:

33. Type 3 at the

Select Command or parameter set (1..4)

to change:

prompt. The

CP1 Function

prompt appears.

34. Type 4 to select RS485 Enable

35. To accept the change, press Enter

36. Press Enter three more times to exit the Modem/Configurable Pin

Settings section of the Configuration Menu.

4) Advanced Modbus Protocol Settings

In the Advanced Modbus Protocol Settings section of the Configuration
Menu you can configure:

• whether the Slave Address is fixed or used as received
• whether to Allow Modbus Broadcasts
• whether to Use MB/TCP 00BH/00AH Exception Responses
• whether to Disable Modbus/TCP Pipeline
Character Timeout values
Message Timeout values
Serial TX delay after RX values
• whether to Swap 4x/0H to get 3x/1x register conversions

Figure 18.

Advanced Modbus Protocol Settings Menu