Slave ip address – B&B Electronics MES1A User Manual

Page 44

Advertising
background image

Configuring the MES1A/B

Manual Documentation Number: MES1A/MES1B-2106m PN7138-rev001

B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com

B&B Electronics Ltd – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com

34

Slave IP Address

Type in the four octets of the IP address of the slaves being addressed.

• If you configure the last octet as 000 the MES1A/B will use the Slave

Address/Unit ID of the slave as part of the IP address. This allows a
Modbus/RTU master (connected through the MES1A/B) to access up to
255 remote Modbus TCP slaves.

• If you configure the last octet for a number between 1 and 254, all slave

polls in this group will be sent to the same IP address.

Advertising
This manual is related to the following products: