Technical data – Lenze 8400 motec Mounting Instructions User Manual

Page 44

Advertising
background image

Technical data

General data and operating conditions

3

l

44

EDK84DGDVBxxx4 DE/EN/FR/ES/IT 5.3

Supply conditions

Mains connection

Power system

TT, TN
(with an earthed
neutral)

Operation permitted without restrictions.

IT

Implement the measure described for IT systems
(remove IT screw).
The machine/system manufacturer is responsible for
compliance with EMC requirements for noise
emission (EN 61800−3) for the machine/plant!
Operation with an integrated safety system is
not permissible.

Motor connection

Motors

EN 60034

Only use motors suitable for inverter operation.
Insulation resistance:
at least û

³1.5 kV, at least du/dt ³5 kV/ms

Length of the motor
cable

< 20 m (Lenze system cable, shielded)

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1

1K3 (−30 ... +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−30 ... +75 °C)

Operation

IEC/EN 60721−3−3

3K3 (−30 ... +55 °C)
Operation at 4 kHz: > +45 °C: Reduce the rated output
current by 2.5 %/°C.
Operation at 8/16 kHz: > +40 °C: Reduce the rated
output current by 2.5 %/°C.

Site altitude

< 4000 m amsl
Above 1000 m amsl reduce the rated output current
by 5 %/ 1000 m.

Pollution

IEC/EN 61800−5−1

Degree of pollution 2

Mechanical

Vibration resistance

(9.81 m/s

2

= 1 g)

Motor mounting

Germanischer
Lloyd

General conditions: Acceleration resistant up to 2 g

IEC/EN 60721−3−3

3M6

Wall mounting
with
E84DZMAWE1

Germanischer
Lloyd

General conditions: Acceleration resistant up to 2 g

IEC/EN 60721−3−3

3M6

Advertising