Software operation

User Interface Dialogs
Registry "ACU Control" − Configure UPS

2

l

12

LDCDP−EPC50ACU EN 4.0

2.3.2

Registry "ACU Control" − Configure UPS

)

Note!

This registry is only shown when the ACU software has been called up via the
system panel. It is not shown when the software is called up by double−clicking
the symbol in the information bar of the Windows task bar.

ACU USV V2.x:

Dialog Box

Value Range

Explanation

Buffer Time [s]

0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the

ACU UPS control unit. Thus, voltage fluctuations are filtered
out.

Delay Time

0 ... 240 s;

infinite

Maximum period of time the industrial PC can be fed by the
battery/capacitor pack, depending on the hardware.

Restart after Delay Time

On/Off

On: Restart or shutdown of the system when the delay time is
up.

UPS Activated

On/Off

On: UPS support activated
Off: UPS support deactivated

Auto off after shutdown

On/Off

On: The ACU UPS control unit is switched off right after the
shutdown of the system. This function requires a system with
ACPI support (ETX−CD).

Backlight off after Power Fail

On/Off

On: Deactivates the backlight of the TFT display in case of a
voltage failure.