Registry "Time Set" − Time Before Shutdown

2

l

14

LDCDP−EPC50ACU EN 4.0

2.3.3

Registry "Time Set" − Time Before Shutdown

ACU UPS Vx.x:

Dialog Box

Value Range

Explanation

Time Before Shutdown

0 ... 60 s

Period of time from identifying a mains failure by the ACU UPS
control unit until shutting down the IPC. This period of time
must be shorter than the delay time (

^ 12) plus the period of

time needed by the IPC to shut down.
Example:
The IPC can be supplied for 100 s by the battery pack and needs
a maximum of 20 s for a safe shutdown.
Delay time = 100 s
Time before shutdown = < 80 s

2.3.4

Registry "Application"− Start External Programs

ACU UPS Vx.x:

While the ACU software counts down the seconds until the IPC is shut down after a voltage
failure, an external program can be started.

Dialog Box

Value Range

Explanation

Executable Application

Path of the executable program file of the application

[Browse]

Search executable program file

Execute Application

On/Off

On: The program file specified in "Executable Application" is
executed.