TECHNICIAN SETUP MENU

Adjustment Options

Factory Default Settings

Tech Setup Steps (Continued from the previous page)

LCD Will Show

TECH SETUP

STEPS CONTINUED

ON THE NEXT PAGE

OFF

Cooling Fan

Delay

The cooling fan

delay setting will

delay the fan from

coming on in cool

mode and keep

running after the

compressor shuts

off for a short time

to save energy in

some systems.

You can select the

Cooling Fan Delay

from OFF, 15, 30, 60

or 90 Seconds.

off

cool FAN DELAY

Next preV done

off

iaq mode cycles

Next preV done

10

iaq mode cycles

Next preV done

OFF

Satisfy

Setpoint

This feature allows

the thermostat to

keep multiple

stages of heat or

cool energized until

setpoint is satisfied.

Use the or

key to turn on or

off.

off

satisfy setpoint

Next preV done

off

Staging delay

Next preV done

off

hum pad 0415

Next preV done

off

uv lamp 02288

Next preV done

off

IAQ CELL 02288

Next preV done RST

This Programmable/Selectable mode will operate the fan 1-4 cycles per
hour, 1-45 minutes per cycle. Once programmed in Tech Setup, to enable
this mode select ‘IAQ’ with the Fan Key. Or you can disable the mode by
selecting ‘ON’ or ‘AUTO’ with the Fan Key.

A Note about IAQ Mode:

2nd

IAQ Mode Cycle

This feature will

configure the fan to

run a selected

number of cycles

“per hour”.

Note: This mode can

be enabled or

disabled at anytime

during normal

operation, by

selecting IAQ mode

with the fan key.

Select OFF, 1,2,3 or 4

with the or

keys.

This sets the number

of cycles per hour

that the IAQ fan

mode will operate.

OFF

1

IAQ Mode Minutes

This allows you to

select the minimum

number of minutes

that the fan will run

“Per Cycle “. The

thermostat will keep

track of fan run time

from normal Heat

and Cool operation.

If additional fan

runtime is needed,

the thermostat will

run the fan to satisfy

the IAQ mode

minutes.

Select 1, 5, 10 ,15

,20 ,30 or 45

minutes.

When IAQ fan mode

is enabled, it will

ensure the fan runs

at least the selected

number of minutes

per IAQ mode cycle.

OFF

Staging Delay

This feature allows a

delay to occur when

a second and third

stage is needed. This

allows the previous

stage extra time to

satisfy setpoint.

Use the or

key to select YES, 5,

10, 15, 30, 45, 60, or

90 minutes.

OFF

Humidity Pad

Reminder

This will remind the

user to change the

humidity pad.

Use the or

key to select OFF,

600, 1000, 1500,

2000. These

represent hours of

heat operation.

UV Lamp

Reminder

Will remind the user

to change the UV

light bulb.

Use the or

key to select OFF,

1YEAR, 2YEAR.

OFF

IAQ Cell

Reminder

Will remind the user

to change the PHI

Cell after 25,000 hrs.

Use the or

key to select OFF,

250. (Stands for

25000 hours)

OFF