Technician setup menu, Filter change reminder, Room temperature calibration – Pro1 T855i Installation manual User Manual

Page 7: Minimum compressor on time, Compressor short cycle delay tech setup steps, Cooling swing, Heating swing, Keypad lockout, Technician setup menu - system operation

Advertising
background image

7

Filter

Change

Reminder

This feature will

flash “FILT” in the

display after the

elapsed run time

to remind the user

to change the

filter. A setting of

“OFF” will disable

this feature.

You can adjust the

filter change

reminder from

“OFF” to 2000

hours of runtime in

50 hour

increments.

OFF

LCD Will Show

Adjustment Options

This feature allows

the installer to

change the

calibration of the

room temperature

display. For example,

if the thermostat

reads 70° and you

would like it to read

72° then select +2.

Room

Temperature

Calibration

You can adjust the

room temperature

display to read -4°F to

+4°F above or below

the factory calibrated

reading.

0 ºF

Minimum

Compressor On

Time

This feature allows the

installer to select the

minimum run time for

the compressor. For

example, a setting of 4

will force the

compressor to run for

at least 4 minutes

every time the

compressor turns on,

regardless of the room

temperature.

You can select the

minimum compressor

run time from “OFF”,

“3”, “4”, or “5” minutes.

If 3, 4, or 5 is selected,

the compressor will run

for at least the selected

time before turning off.

OFF

Compressor

Short Cycle

Delay

Tech Setup Steps

The compressor short

cycle delay protects

the compressor from

“short cycling”. This

feature will not allow

the compressor to be

turned on for 5

minutes after it was

last turned off.

Selecting “ON” will not

allow the compressor

to be turned on for 5

minutes after the last

time the compressor

was on. Select “OFF” to

remove this delay.

ON

Cooling

Swing

The swing setting

often called “cycle

rate”, “differential” or

“anticipation” is

adjustable. A smaller

swing setting will

cause more frequent

cycles and a larger

swing setting will

cause fewer cycles.

The heating swing

setting is adjustable

from 0.2°F to 2°F. For

example: A swing

setting of 0.5°F will

turn the heating on at

approximately 0.5°F

below the setpoint and

turn the heating off at

approximately 0.5°F

above the setpoint.

The cooling swing

setting is adjustable

from 0.2°F to 2°F.

For example: A swing

setting of 0.5°F will

turn the cooling on at

approximately 0.5°F

above the setpoint

and turn the cooling

off at approximately

0.5°F below the

setpoint.

0.5 ºF

0.4 ºF

Heating

Swing

The swing setting

often called “cycle rate”,

“differential” or

“anticipation” is

adjustable. A smaller

swing setting will

cause more frequent

cycles and a larger

swing setting will

cause fewer cycles.

TECH SETUP

STEPS CONTINUED

ON THE NEXT PAGE

Keypad

Lockout

Keypad lockout allows

you to configure the

thermostat so that

none or some of the

keys do not function.

OF = keypad lockout

has been disabled.
PA = partial keypad

lockout, which locks all

the keys except the

or keys.
FU = Full keypad

lockout, which locks

out all the keys.

See note below on
operation.

PA

Technician Setup Menu - System Operation

This thermostat has a technician setup menu

for easy installer configuration. To setup the

thermostat for your particular application:

1.
2.

Factory Default Setting

Configure the installer options as desired,

using the table below.

Use the or keys to

change settings and the PREV or NEXT key

to move from one step to another.

Note: Only press DONE key when you want

to exit the Technician Setup options.

Press DONE key to exit.

+

-

3.

Press MENU button.

TECHNICIAN SETUP MENU

Press and hold TECH

button for 3 seconds. This 3 second delay

is designed so that homeowners do not

accidentally access the installer settings.

4.

Note:

The function of activating your Keypad Lockout choice takes place

after you have exited Tech Setup. If you do not perform this activation
procedure, all keys will function freely. To lock the keypad hold down the
and keys for 3 seconds.You will see a lock in the display. To unlock
the keypad hold down the and keys for 3 seconds.

OFF

se

filter

0000

next preV done RST

cal

0

CALIBRATE

NEXT preV done

F

OFF

MIN COMP ON TIME

NEXT preV done

ON

COMPRESSOR DELAY

NEXT preV done

C0

0F

COoling Swing

NEXT preV done

0.5

Heating swing

NEXT preV done

0.4

keypad lockout

NEXT preV done

pa

Advertising