Technician setup menu, Cooling temperature setpoint limit, ºf or ºc – Pro1 T855i Installation manual User Manual

Page 8: 12 or 24 hour clock, Program options, Fan operation, Morning recovery, Time periods

Advertising
background image

8

The second stage will turn on at 2x the swing setting. The second stage will turn off when

1x the swing is reached. For example, if the swing setting is .5 degrees for heating and the

thermostat is set at 70ºF, the first stage will turn on at approximately 69.5ºF. The second

stage will turn on at 69.0ºF. The second stage will turn off at 69.5ºF and the first will turn off

at 70.5ºF. If third stage is used, it will turn on at 3x the swing and turn off at approximately 2x the swing.

Swing Setting Tip

Heating

Temperature

Setpoint Limit

This feature allows

you to set a

maximum heat

setpoint value. The

setpoint tempera-

ture cannot be

raised above this

value.

Use the or

key to select

the maximum heat

setpoint.

Range 44ºF - 90ºF

90ºF

LCD Will Show

Adjustment Options

Tech Setup Steps (Continued from the previous page)

Factory Default Setting

Cooling

Temperature

Setpoint Limit

This feature allows

you to set a

minimum cool

setpoint value. The

setpoint tempera-

ture cannot be

lowered below this

value.

Use the or

key to select the

minimum cool

setpoint.

Range 44ºF - 90ºF

44ºF

ºF or ºC

This feature allows

you to display

temperatures in

either Fahrenheit

or Celsius.

ºF for Fahrenheit

ºC for Celsius

ºF

TECHNICIAN SETUP MENU

12 or 24

Hour Clock

Use the or

key to select 12 or

24 hour clock.

You can select

either a 12 or 24

hour clock setting.

12 Hour Clock

TECH SETUP

STEPS CONTINUED

ON THE NEXT PAGE

Program

Options

You can configure this

thermostat to have a

7 day program, a

5+1+1 program or

nonprogrammable.

Use the or

key to select 7d for 7

day, 5d for 5+1+1, or

0d for

nonprogrammable.

7d

HEAT SET LIMIT

NEXT preV done

HE

90

COOL SET LIMIT

NEXT preV done

c0

44

f or c set

NEXT preV done

80

44

F

F

CLOCK SET

NEXT preV done

12H

Fan

Operation

GAS

Select GAS for

systems that control

the fan during a call

for heat.

Select ELEC to have

the thermostat

control the fan

during a call for heat.

GAS

or

ELEC

FAN OPERATION

NEXT preV done

GAS

Morning

Recovery

Use the or

key to turn on or off.

OFF

This feature will start

heating early to bring

the building

temperature to its

programmed

setpoint by the

beginning of the time

period -

(WAKE, OCCUPIED).

MORNING recovery

NEXT preV done

OFF

program

NEXT preV done

5

Time Periods

4

You can configure

this thermostat to

have 2 or 4

programmable

time periods per

day.

2 time periods is

Occupied/Unoccupied

4 time periods are

Wake, Leave, Return

Sleep.

Use the or

key to select 2 or 4

time periods per day.

Time periods a day

NEXT preV done

4