En50160 advanced setup – SATEC EM920 Operation Manual User Manual

Page 125

Advertising
background image

Chapter 5 Configuring the EM920

Configuring the EN50160 Recorders

EM920 Power Quality and Revenue Meter

125

The default EN50160 compliance limits are shown in the
picture above. You can change the number of the evaluated
harmonics and interharmonics via the

EN50160 Advanced

Setup

.

EN50160 Advanced Setup

The EN50160 Advanced Setup allows you to configure the
EN50160 evaluation options in your meter.

To configure the EN50160 evaluation options:

1. Select Memory/Log from the Meter Setup menu, and

then click on the EN50160 Advanced Setup tab.

2. Change the EN50160 evaluation options if required.

3. Download your setup to the device.

The default EN50160 evaluation options set in your device
are shown in the picture below.

The available options are listed in the following table.

Option Range

Default

Description

EN50160 Compliance Statistics

Evaluation

Disabled, Enabled Enabled

Enables the EN50160 evaluation

Evaluation Period

Daily, Weekly

Weekly

Defines the EN50160 statistics evaluation

period

First Day of the
Week

Sunday-Saturday Sunday

Defines the first day of the week for
statistics evaluated on a weekly basis

EN50160 Harmonics Survey

Evaluation Disabled,

Enabled

Enabled

Enables the harmonics survey log

Evaluation Period

Daily, Weekly

Weekly

Defines the harmonics survey evaluation

period

Advertising