Output of energy pulses through relay outputs – SATEC EM920 Operation Manual User Manual

Page 89

Advertising
background image

Chapter 5 Configuring the EM920

General Meter Setup

EM920 Power Quality and Revenue Meter

89

Parameter Options Default

Description

Polarity NORMAL

(N.O.)

INVERTING (N.C.)

NORMAL

Normal polarity: the relay is normally de-
energized in its non-active state and is
energized in its active (operated) state.
Inverting polarity: the relay is normally
energized in its non-active state and is de-
energized in its active (operated) state. It is
called failsafe relay operation.

Retentive
mode

NO
YES

NO

Applicable for latched relays only.
Non-retentive mode: the relay always returns to
its non-active state upon power up.
Retentive mode: the relay status is restored to
what it was prior to loss of power.

Pulse width

20-1000 ms

100 ms

The actual pulse width is a multiple of the 1/2-
cycle time rounded to the nearest bigger value.
The pause time between pulses is equal to the
pulse width.

Pulse source

NONE
kWh IMP
kWh EXP
kvarh IMP
kvarh EXP
kvarh TOT
kVAh

NONE

Links a pulse relay to the internal energy pulse
source. The relay must be set into either pulse,
or KYZ mode.

Pulse rate,
kWh/Pulse

0.1-1000.0 1.0

kWh/Pulse

Defines the pulse weight in kWh units per pulse.

Output of Energy Pulses through Relay Outputs

To generate energy pulses through a relay output:

1. Set a relay to either pulse, or KYZ mode, and then

select a polarity (active pulse edge) for energy pulses
and a pulse width.

2. Select a source accumulator (type of energy) and the

pulse rate for your output.

3. Send your new setup to the meter.