Chapter 6 Device Control and Upgrading

Reset of Billing Maximum Demands

140

EM920 Power Quality and Revenue Meter

Reset of Billing Maximum Demands

A demand reset signals an end of the present billing period
and causes the following automatic actions:

• increments the number of the recorded billing periods.

This number will roll over to zero after 99 demand
resets;

• copies the present billing period data - maximum

demand, cumulative maximum demand and energy
values, and the number of days since last demand
reset, - to the previous billing period registers;

• adds the present maximum demand values to the

cumulative maximum demands;

• clears the number of days since last demand reset;

• clears the present maximum demand values;

• records the new previous billing period data -

maximum demand, cumulative maximum demand and
energy values, - to the monthly profile data log.

NOTE

You will not be allowed to reset the billing maximum
demands twice within one calendar day. The EM920 uses a
one-day protection lockout time to avoid subsequent demand
resets.

Using the Front Display

To allow demand reset via the front display, the manual reset
must be enabled by the End of Billing Period setting (see

Device Options and Mode Control

in Chapter 5).

To reset billing maximum demands:

1. Press the DEMAND RESET button for more than 2

seconds until the maximum demand reset menu is
open.

2. Press briefly SELECT/ENTER button to highlight the

“Do” entry.

3. Press and hold the SELECT/ENTER button for more

than 5 seconds until the “Do” entry is replaced with
“Done” indicating that the operation is complete.

4. Release the button.

Using PAS

To allow demand reset via Pas, the reset via communications
must be enabled by the End of Billing Period setting (see

Device Options and Mode Control

in Chapter 5).

To reset billing maximum demands:

1. Select Reset from the Monitor menu.

2. Click on the Reset Billing/TOU Max. Demands button.

3. Confirm your command.