Upgrading meter firmware – SATEC EM920 Operation Manual User Manual

Page 143

Advertising
background image

Chapter 6 Device Control and Upgrading

Upgrading Meter Firmware

EM920 Power Quality and Revenue Meter

143

To change the status of an event flag:

1. In the “Status” box, select the desired flag status.

2. Click on Send.

Upgrading Meter Firmware

You can upgrade device firmware through any communication
port installed in your meter: a serial port, USB, wireless
GSM/GPRS modem, or via the Internet.

Downloading firmware is only supported through the Modbus
RTU/ASCII and Modbus/TCP protocols. If you are connected
to the meter via a serial port, ensure that it operates in
Modbus mode. It is also recommended to set the serial port
baud rate to 115,200 bps. See

Configuring Communications

on how to remotely change the protocol and baud rate in
your meter.

To download a firmware file to your meter:

1. Check the On-line button on the PAS toolbar, select

Flash Downloader from the Monitor menu, and then
confirm changes.

2. Point to the firmware upgrade file, click Open, and

then confirm upgrading the meter.

3. When asked for the password, type the meter

password, and click OK.

4. Wait until PAS completes downloading the file. It takes

about 9-10 minutes at 115,200 bps via a serial port, or
about 20 seconds via a USB port, to download the file
to the meter.