Measurement specifications, Appendix a technical specifications, Series pm174 powermeters – SATEC PM174 Manual User Manual

Page 133

Advertising
background image

Appendix A Technical
Specifications

Series PM174 Powermeters

133

Measurement Specifications

Accuracy

Parameter

Full Scale @ Input
Range

%
Reading

% FS

Conditions

Range

Voltage

120VxPT @ 120V
400VxPT @ 690V

0.2

0.01

10% to 120% FS 0 to 1,150,000 V

Starting voltage
1.5% FS @ 120V
1.5% FS @ 690V

Line current

CT

0.2

0.02

1% - 200% FS

0 to 40,000 A
Starting current 0.1% FS

Active power

0.36

×PT×CT @ 120V

1.2

×PT×CT @ 690V

0.2 0.02

|PF|

≥ 0.5

1

-10,000,000 kW to
+10,000,000 kW

Reactive power

0.36

×PT×CT @ 120V

1.2

×PT×CT @ 690V

0.3 0.04

|PF|

≤ 0.9

1

-10,000,000 kvar to
+10,000,000 kvar

Apparent power 0.36×PT×CT @ 120V

1.2

×PT×CT @ 690V

0.2 0.02

|PF|

≥ 0.5

1

0 to 10,000,000 kVA

Power factor

1.000

0.2

|PF|

≥ 0.5,

I

≥ 2% FSI

-0.999 to +1.000

Frequency

0.02

40 Hz to 70 Hz

Total Harmonic
Distortion, THD
V (I), %Vf (%If)

999.9 1.5

0.1

THD

≥ 1%,

V (I) ≥ 10% FSV

(FSI)

0 to 999.9

Total Demand
Distortion, TDD,
%

100

1.5

TDD

≥ 1%,

I

≥ 10% FSI

0 to 100

Active energy
Import & Export

Class 0.2S under conditions as per IEC
62053-22:2003

0 to 999,999.999 MWh

Reactive energy
Import & Export

Class 0.2S under conditions as per IEC
62053-22:2003, |PF|

≤ 0.9

0 to 999,999.999 Mvarh

Apparent energy

Class 0.2S under conditions as per IEC
62053-22:2003

0 to 999,999.999 MVAh

1

@ 80% to 120% of voltage FS, 1% to 200% of current FS, and frequency 50/60 Hz

PT - external potential transformer ratio
CT - primary current rating of external current transformer
FSV - voltage full scale
FSI - current full scale
Vf - fundamental voltage
If - fundamental current

NOTES

1. Accuracy is expressed as

± (percentage of reading + percentage of full scale) ±

1 digit. This does not include inaccuracies introduced by the user's potential and
current transformers. Accuracy calculated at 1second average.
2. Specifications assume: voltage and current waveforms with THD

≤ 5% for kvar,

kVA and PF, and reference operating temperature 20

°C - 26°C.

3. Measurement error is typically less than the maximum error indicated.