SATEC PM174 Manual User Manual

Page 73

Advertising
background image

Chapter 4 PAS
Application Software

General Meter Setup

Series PM174 Powermeters

73

The available relay options are shown in the following table:

Parameter Options

Default

Description
Unlatched mode: the relay goes into its

active state when the control setpoint is
in active (operated) state, and returns
into its non-active state when the
setpoint is released.

Operation

mode

UNLATHCED

LATCHED
PULSE
KYZ

UNLATCHED

Latched mode: the relay goes into its

active state when the control setpoint
goes into active state and remains in
the active state until it is returned into
its non-active state by a remote
command.
Pulse mode: the relay goes into its

active state for the specified time, goes
into non-active state for the specified
time and remains in the non-active
state.
KYZ mode: the relay generates

transition pulses. The relay output state
is changed upon each command and
remains in this state until the next
command.

Polarity NORMAL

(N.O.)
INVERTING
(N.C.)

NORMAL

With normal polarity, the relay is

normally de-energized in its non-active
state and is energized in its active
(operated) state.
With inverting polarity, the relay is

normally energized in its non-active
state and is de-energized in its active
(operated) state. It is called failsafe
relay operation.