SATEC PM174 Manual User Manual

Page 45

Advertising
background image

Chapter 3 Display
Operations

Menu Operations

Series PM174 Powermeters

45

2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to store your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

The following table lists available options.

Label Parameter

Options Default Description

ConF Wiring

connection

(configuration) mode

See “Basic
Meter
Setup” in
Chapter 4

4Ln3

The wiring connection of the
device

Pt

PT ratio

1.0-6500.0 1.0

The phase potential

transformer’s primary to
secondary ratio

Pt.F

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor.
Used in extra high voltage
networks to accommodate the
PT ratio for 500 kV and higher
networks.

U.SEC Nominal

secondary

voltage

10-690 V

120 V

The nominal secondary line-to-
neutral (in 4LN3, 3LN3 and
3BLN3 wiring modes) or line-to-
line (in 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3 and 3DIR modes)
voltage. Used as a reference
voltage for the IEEE 1159
Power Quality recorder.

Ct

CT primary current

1-20000 A

5 A

The primary rating of the phase

current transformer

d.P

Power block demand
period

1, 2, 5, 10,
15, 20, 30,
60 min,
E=external
sync

30 min

The length of the demand
period for power demand
calculations. If the external
synchronization is selected, a
pulse front on the digital input
DI1 denotes the start of the

demand interval.

nd.P

The number of blocks in
the sliding window

1-15

1

The number of blocks to be
averaged for sliding window
demands

Ad.P

Ampere, volt and THD

demand period

0-1800 sec 900 sec

The length of the demand

period for ampere, volt and
THD demand calculations

Freq

Nominal frequency

50,60 Hz

60 Hz

The nominal line frequency

LoAd

Maximum demand load
current

0-20000 A

0

The maximum demand load
current (0 = CT primary)

Ì

Always specify the wiring mode and transformer ratings prior to

setting up setpoints and analog outputs.

Ì

The maximum value for the product of the phase CT primary

current and PT ratio is 57,500,000. If the product is greater, power
readings are zeroed.