Chapter 4 PAS
Application Software

Configuring Recorders

Series PM174 Powermeters

95

3. Select the maximum number of records you want to be recorded

in the file.

The number of records in the waveform log file needed to
store one waveform event (series) is defined as follows:

Number of Records per Series = Sampling Rate (Samples
per Cycle) x Number of Cycles per Event / 512

The total number of records you must allocate to store the

required number of events (series) is defined as follows:

Number of Records = Number of Records per Series x

Number of Series

For example, if you want to record a 64-cycle waveform sampled
at a rate of 32 samples per cycle, the number of records required
for one waveform series would be:

Number of Records per Series = (32 x 64)/512 = 4.

If you want to allocate space sufficient to store 20 waveform
events (series), you should set up the waveform log file for 4 x 20
= 80 records.

4. Click OK, and send your setup to the meter or save to the

database.

5. Click “Setup Recorder”, or click on the “Waveform Recorder” tab.

The following table lists available waveform options.

Option Format/Range Description
Samples per Cycle 32, 64, 128

Waveform sampling rate

Cycles per Series 16-2560 (32 samples/cycle),

8-1280 (64 samples/cycle),
4-640 (128 samples/cycle)

Defines the total duration of the
waveform per event/series

Before Cycles

1-20

Defines the number of cycles to be

recorded prior to event

Num. of Channels 1-6

The number of the simultaneously
recorded channels

6. Select the sampling rate for waveforms.

Advertising