Fuse specifications, Factory contacts and tech support – TCI HGP User Manual

Page 12

Advertising
background image

S T A N D A R D O P T I O N ( S )

Standard Option (S)

HGP IOM Manual

12

Fuse Specifications

Table 1a lists the specifications for the fuses in the HGP. Refer also to the drawings and other
information shipped with the unit.

Table 1a – Fuse Specifications for HGP 480 Volt Models

HG7 Rating

(HP)

kVar

Max Branch Circuit

Fuse

Max Line Fusing

(J or T)

(J, T or L)

5

1.3

20

30

7.5

3

20

30

10

3

20

30

15

5

30

30

20

6

30

60

25

8

30

60

30

10

30

60

40

15

30

60

50

15

30

80

60

20

50

100

75

25

50

125

100

30

60

150

125

40

80

200

150

45

100

225

200

60

125

300

250

75

150

375

300

90

175

450

350

105

200

500

NOTE: Customers must provide line fusing to complete SCCR 100KA rating.

Factory Contacts and Tech Support

For technical support, contact your local TCI distributor or sales representative. You can contact TCI
directly at 800-TCI-8282. Select "Customer Service" or "Tech Support" and have your HGP filter
nameplate information available.

Advertising