F I T L E R A N D F U S E M O N I T O R O P E R A T I O N

Filter and Fuse Monitor Operation

HGP IOM Manual

21

Fuse Monitor Operation and Relay Specifications

The fuse monitor relay contact is a single pole, double throw (SPDT) dry type contact. Terminal Block
connection TBa-7 is the common connection, TBa-6 is the Normally Closed (NC) connection, and
TBa-8 is the Normally Open (NO) Connection.

Table 2 – Fuse Monitor Operation Modes and Output Table

Operating State

Input
Voltage

HGP
Filter

N.C. Relay Contact
(TBa-6 TBa-7)

N.O. Relay Contact
(TBa-7 TBa-8)

No Input Line Voltage

Not Present

X*

Closed

Open

Input Line Voltage has
Missing Phase

Phase Loss

X*

Closed

Open

Input Line Voltage has
Phase Reversal

Phase
Reversal

X*

Closed

Open

HGP Filter has Blown
Trap Fuse

Nominal

Blown
Trap Fuse

Closed

Open

HGP Fuse Monitor has
Blown Fuse

Nominal

Blown
Monitor
Fuse

Closed

Open

HGP Filter Contactor is
Open

Nominal

Contactor
Open

Closed

Open

Nominal

Nominal

Contactor
Closed

Open

Closed

*X = don’t care condition

Table 3 – HGP Filter Fuse Monitor Relay Contact Specifications

Relay Contact

Location

Contact Rating

Normally Open Contact

(TBa-7 TBa-8)

10A Resistive @ 240V AC
1/3HP @ 120/240V AC

Normally Closed Contact

(TBa-6 TBa-7)

10A Resistive @ 240V AC
1/6HP @ 120/240V AC

Figure 3 – HGP Filter Fuse Monitor Typical Connection Circuit Diagram