1) Verify unit external connections

• Phase A, B, C power connection,

with positive A-B-C phase rotation expected

• CT H1 Terminal is pointing toward the source

• CT feedback on phases A & C to TB-1
• Leave CT shorting bars in place on TB-1
• With the HGA circuit breaker open,

energize the source to the HGA

• Close the HGA circuit breaker

• Fans and HMI should come on in < 5 seconds
• HMI will start on Home screen
• Load(s) have an integral 5% line reactance or

equivalent dc bus choke

Warning

Hazardous voltages are present when
unit is energized


NOTE: Language Selection

• The active filter supports several languages

including English, French and Spanish

• Press “Setup” to navigate to Setup screen and

press the “Language Setup” button.

• Select language setting from the language setup

pop-up screen.


2) Converter check - 1

• Press “Setup” to navigate to Setup screen

• Ensure that “Auto Start En,” “Harmonic

Correct En,” and “PWR Fact Correct En”
buttons are off (blue color)

• If they are ON (green) press them to toggle to OFF

(blue)

• Press “Save Settings”

• Press “Status” to navigate to Status screen
• Press “Home” to navigate to Home screen


NOTE: Built In Sensor Wiring Error Detection

• The active filter has an automatic sensor wiring

error detection algorithm built in to the controls.

• If a sensor wiring error is detected please reference

the Sensor Error Auto Detection section on page
93.

!