9


7) Remove CT shorting bars

• Press “Stop” to turn off unit
• Disconnect power from cabinet

o

Turn off the built in door breaker AND

o

Turn off the upstream feeder breaker

• Open the cabinet door and remove shorting bars

from CTs connected to TB-1

Warning

Lethal voltages may be present. Wait 5
minutes for DC bus voltage to drop to
safe levels.

Warning

Check for voltage in cabinet with a
DMM before working inside cabinet.


8) Current polarity - 1

• Power up unit
• From Home screen press “Run” to turn on unit
• Press “Status” to navigate to Status screen
• Select “Vline/Iline” screen

• Note: Lightly loaded conditions (less than 20% CT

rating) will not have enough current to
show up on Iline plot

• Check that Phase A to Neutral voltage peak lines

up with Phase A current (use zoom if necessary)

• Check that Phase C to Neutral voltage peak lines

up with Phase C current

• Power system down and check CT installation

location and orientation if Phase A plots differ
significantly from Phase C plots

Warning

Improper operation and damage may
occur if CTs are installed incorrectly.


9) Current Polarity – 2

• Navigate to Status screen
• Navigate to Line/Load status
• Verify that “Volts,” “Current,” “Power,” “I THD,"

and “V THD” match expected values for the
power system

• If they do not, verify CTs are correctly installed

Warning

Improper operation and damage may
occur if CTs are installed incorrectly.