Troubleshooting

HarmonicGuard Active Filter Fault

If the display indicates a fault has occurred proceed to the fault screen by choosing the “Fault” menu screen
button. To see if this is a recurring fault hit the “History” button from inside the “Fault” screen. To clear a
fault press the “Reset” button from inside the “Fault” Screen or the “Stop” button from any screen.


Warning

Only qualified electricians should carry out all electrical installation & maintenance work on the HGA.

Disconnect all sources of power to the drive and HGA before working on the equipment. Do not
attempt any work on a powered HGA.

This HGA unit contains high voltages and capacitors. Wait at least five minutes after disconnecting
power from the filter before attempting to service the conditioner. Check for zero voltage between all
terminals on the capacitors. Also, check for zero voltage between all phases of the input and output
lines. All maintenance and troubleshooting must be done by a qualified electrician. Failure to follow
standard safety procedures may result in death or serious injury. Unless an external disconnect
means has been provided everything ahead of the filter circuit breaker, including the reactors,
will still be energized.

Interface Module Problem

The Interface Module is comprised of four major components; the HMI display, the Interface PCB, the
cabling and an optional Gateway. The Interface PCB contains diagnostic LEDs. The locations of the LEDs
are shown in Figure 8.3, and their functions are listed in Table 8.1.

Figure 8.3 – Communications Board LED placement

Table 8.1 – LED Functions

LED

LED Color

Description (LED Color)

D1

Green

AUX 1

D3

Green

AUX 2

D4

Green

Running Relay Energized

D5

Green

Power-On Relay Energized

D6

Green

Fault Relay Energized

D7

Green

Current Limit Relay Energized

D12

Green

RS485 Communication is active from converter

D13

Orange

RS485 Communication is active to converter

D14

Green

Input Run Command Present