TCI HGA Manual User Manual

Page 83

Advertising
background image

83

Figure 7.8 – VLine & ILine Waveform Plot of a Properly Connected

HarmonicGuard Active filter (unit in stopped state)

Note: The example VLine & ILine Waveform Plot screens apply to rectifier loads only. For low power factor
loads the VLine & ILine waveform screen will appear different.

Table 7.8 shows what the VLine & ILine Waveform Plot Sub Screen would look like with various
connection errors present in the system.

Table 7.8 – VLine & ILine Waveform Plot Screen Examples when

Typical Connections Errors Present in System

VLine & ILine Waveform Plot Sub Screen with
Rectifier Load

Connection
Error
Description

Connection Error
Resolution

Phase rotation is
Incorrect:

Phase A leads
Phase C instead
of Phase C
leading Phase A.

To correct swap
Phase A and Phase
C HarmonicGuard
Active filter power
connections AND
swap Phase A and
Phase C system CT
current feedback
then recheck plot.