Testing, Do not supply the system with electric current, Taking the ohm readings – WarmlyYours TempZone FLEX (Twin) Conductor 120V or 240V User Manual

Page 8: Record the ohm readings, Go by the numbers

Advertising
background image

DO NOT SUPPLY THE SYSTEM WITH

ELECTRIC CURRENT

All testing is done with a digital Ohmmeter. Supplying the system with a 120 volt or 240

volt electric current before the installation is complete is not needed to test the system.

Taking the Ohm Readings

The electrical resistance of the Heating Roll(s) must be checked before you start, and

monitored throughout the installation process to ensure there has been no damage

causing shorts or breaks. We recommend at least three readings be taken:
1. Before starting installation.
2. After securing the Heating Roll(s) in place on the subfloor.
3. After installing the flooring surface above the Heating Roll(s).

Record the Ohm Readings

The Value on the UL label should be within +/- 15% variance of the original measurement

indicated on the label. The electrician should carefully mark the initial Ohm reading taken

onto the warranty card. Should the initial Ohm reading be outside the 15% +/- variance,

refer to the electrical trouble shooting section on Page 14, or call Technical Support at

(800) 875-5285.

Go by the Numbers

The Ohm resistance should be measured from the inner core of the yellow (120V), or

red (240V) lead wire at one end, to the inner core of the Black lead wire at the other end.

Make sure that the probe of the Ohmmeter does not touch the tinned sheath wire at either

end. Even your body’s electrical resistance can affect the reading if you touch the meter

poles. Do not hold the wires onto the probes with your fingers. A digital meter is easier to

use and strongly recommended. It is wise to verify that the batteries of the Ohmmeter are

good. Set your Ohmmeter to measure resistance in the range of 0 to 200 Ohms.

On some smaller rolls, it may be necessary to set the ohm meter to the next higher range

of measurment to get an accurate ohm reading.

Three (3) Ohm Readings should be taken for each roll of WarmlyYours TempZone at each

stage of the installation and recorded in the table below.

1)

Core to Core - This is the reading between the two inner conductors on the lead wires.

2)

Core to Sheath Yellow / Red Lead - This is the reading between the inner core and

the outer ground sheath on the lead wire. This reading should be infinity.

3)

Core to Sheath Black Lead - This is the reading between the inner core and the outer

ground sheath on the lead wire at the finish point of the roll. This reading should be

infinity.

After the installation, if necessary, the position of a break can be found with a time domain

reflectometer. Repair kits and guidance are available from the WarmlyYours support line.

Details of how to repair a damaged Heating Element are also available on our web site at

http://www.warmlyyours.com/en-US/support.

7

Testing

Yellow

or Red

Ground

Ground

Yellow

or Red

Black

Black

Yellow

or Red

Ground

Ground

Yellow

or Red

Black

Black

Yellow

or Red

Ground

Ground

Yellow

or Red

Black

Black

Core to Core

Core to Sheath

Core to Sheath

Catalog Number

Voltage

Usage

Refer to

Instructions

A ground fault

protection device

must be used with

this heating device.

Wattage

Serial Number

Advertising