Rockwell Automation 140G-Rx Installation Instruction-140G-R User Manual

Page 12

Advertising
background image

DIR 1000682R0002 (L5757)

(12)

- If the undervoltage release is installed, disassemble the coil support and unload the springs of the operating mechanism by

closing and opening the circuit-breaker.

Fig. 20

8.3.5. Mechanical operating mechanism

- Clean the points indicated in figure 21. Use a cleaning product such as Henkel’s 273471 or equivalent if there is a heavy coat-

ing of dirt.

- Lubricate the opening and closing latches and the shafts in the points indicated in figure 21.

- Make sure that the opening and closing shafts are free to turn.

Fig. 21

8.3.6. Electrical and mechanical accessories

- Make sure that the accessories are securely fixed to the circuit-breaker.

- Make sure that the electrical accessories are correctly connected to the circuit-breaker.

- Gearmotor: after every 10000 operations, check the brushes for wear and replace the gearmotor if necessary.

- Make sure that the releases (opening/undervoltage/closing) are in good conditions (absence of excessive wear, overheating,

breakages) Fig. 22.

Make sure that the mechanical operation counter functions correctly (if applicable) by operating the circuit-breaker.

17.7 lb-in
2 Nm

2

Warning

lever

1

1

Fig. 22

WARNING: warning lever has to be activated only in case of coils set substitution. Do not operate it in other

conditions