- If the undervoltage release is installed, disassemble the coil support and unload the springs of the operating mechanism by

closing and opening the circuit-breaker.

Fig. 26
8.4.5. Mechanical operating mechanism

- Clean (use a cleaning product such as Henkel’s 273471 or equivalent if there is a heavy coating of dirt) and lubricate (in the

points indicated in figure 27, det. A, as per the First Level) the shafts and opening closing latches.

- Clean (use a cleaning product such as Henkel’s 273471 or equivalent if there is a heavy coating of dirt) and lubricate the operat-

ing shaft supports, including those on the sides of the circuit-breaker (see figure 27, det. B).

- Make sure that the opening and closing shafts are free to turn.

det.A

det.B

Fig. 27

- Contact AB if the springs are deformed or tarnished, if rings are missing or if the control is excessively worn.