8.4.6. Electrical and mechanical accessories

- Make sure that the accessories are securely fixed to the circuit-breaker.

- Make sure that the electrical accessories are correctly connected to the circuit-breaker.

- Gearmotor: after every 10000 operations, check the brushes for wear and replace the gearmotor if necessary.

- Make sure that the releases (

opening/undervoltage/closing

) are in good conditions (absence of excessive wear, overheating,

breakages) Fig. 28.

- Make sure that the mechanical operation counter functions correctly (if applicable) by operating the circuit-breaker.

17.7 lb-in
2 Nm

2

Warning

lever

1

1

Fig. 28

8.4.7. Protection releases

- -Power the protection release with a battery unit.

- Make sure that the protection release functions correctly: release test with the “Trip Test”.

- Make sure that the front leds do not indicate the presence of alarms.

- Make sure that the cables are correctly connected to the release modules and to the release itself (if applicable).

- Remove the battery unit from the relay upon termination.

8.4.8. Maintenance operations; final inspections

- Fit all the parts back in place and re-connect the auxiliary power supply if necessary.

- Re-assemble the escutcheon plate as shown in figure 30.

9.7 lb-in

1.1 Nm

Fig. 29

- Using the different auxiliaries in succession, perform the operations 10 times:

- Opening (in both the local and remote modes, if applicable)

- Closing (in both the local and remote modes, if applicable)

- Release by means of the trip test via relay

- Check the operations in accordance with the following sequence:

- Open - Springs unloaded

- Open - Springs loaded

- Closed - Springs unloaded

- Closed - Springs loaded

- Make sure that the accessories (if installed) function correctly

- Make sure that the gearmotor (if installed) functions correctly

- Make sure that the undervoltage release functions correctly (if installed)

- Make sure that the shunt opening release functions correctly (if installed)

- Make sure that the shunt closing release functions correctly (if installed)

- Make sure that the circuit-breaker's auxiliary contacts function correctly (if installed)

- Make sure that the lock for circuit-breaker in open position (key or padlock) functions correctly (if installed)

WARNING: warning lever has to be activated only in case of coils set substitution. Do not operate it in other