(7)

6. Putting into service

6.1 General procedures

– Make sure that the power connections to the circuit-breaker terminals are tight

– Perform al the preparatory operations on the release

– Make sure that the power supply voltage of the auxiliary circuits is between 85% and 110% of the rated voltage of the electrical applications

– To avoid temperature rises, make sure that there is sufficient air exchange in the installation area

– Also perform the inspections indicated in the following table.

Item inspected

1 Manual operating mechanism


2 Gearmotor (if provided)

3 Undervoltage release

(if provided)

4 Shunt closing release (if provided)

5 Shunt opening release (if provided).

6 Lock for circuit-breaker in open position

(key or padlock)


7 Auxiliary circuit-breaker contacts

Procedure

Perform a few opening, closing and release

operations (see chap. 7.2).
WARNING

When there is an undervoltage release, the cir-

cuit-breaker can only be closed after the release

itself has been electrically energized.
Supply the spring loading gearmotor at the

relative rated voltage.

Perform a few closing and opening operations.

Note. Supply the undervoltage release at the

relative rated voltage (if provided).
Supply the undervoltage release at the relative

rated voltage and perform the circuit-breaker

closing operation.

Turn off the voltage supply to the release.

Supply the undervoltage release at the relative

rated voltage and perform the circuit-breaker

closing operation.
Close the circuit-breaker.

Supply the shunt opening release at the relative

rated voltage.
Open the circuit-breaker.

Power the shunt closing release at the its

rated voltage.
Open the circuit-breaker, turn the key and

remove it. Attempt the circuit-breaker closing

operation.
Insert the auxiliary contacts into appropriate

signalling circuits. Perform a few circuit-breaker

closing and opening operations.

Successful check

The spring loading lever moves normally.

The springs are loaded normally.

The signals are normal.

The gearmotor stops when the springs have

been loaded.

The gearmotor reloads the springs after each
closing operation.

The circuit-breaker closes normally. The signals

are normal.

The circuit-breaker opens. The signal changes

over.

The circuit-breaker opens normally. The signals

are normal.

The circuit-breaker closes normally. The signals

are normal.

Both manual and electrical closing are pre-

vented.

Signalling occurs normally.