9. Measures to be taken if operating faults occur

The circuit-breaker fails to open when the opening pushbutton is pressed

Faults

The circuit-breaker fails to open because opening coil has tripped

The circuit-breaker fails to open because undervoltage release undervoltage has tripped

The circuit-breaker fails to open when the protection relay release test is performed

The circuit-breaker fails to close when the closing pushbutton is pressed

The circuit-breaker fails to close because closing coil has tripped

The closing springs cannot be loaded with the manual loading lever

The closing springs cannot be loaded with the spring-loading motor

The circuit-breaker cannot be locked in the open position

Possible causes

Checks and solutions

The opening solenoid of the relay is not

connected properly

Make sure that the opening solenoid is con-

nected correctly

• • •

Relay tripping signal not reset

Press the mechanical pushbutton to reset the

relay tripping signal

Supply votage of the auxiliary circuits too

low

Measure the voltage: it must not be less than

85% of the rated voltage of the coil

Supply voltage different from the value indi-

cated on the nameplate of these releases

Check the voltage indicated on the nameplate of

the releases

Faulty switching circuit

Check the connections, fuses, interlocks, protec-

tion switches and accept contacts

Loose clamping screws of the wires and

auxiliary circuits

Make sure that the wire clamping screws are

tight

Incorrect electrical connections in the

power supply circuit

Check the connections with the relative func-

tional diagram

Coil damaged

Replace the coil

Operating mechanism locked

Operate in the manual mode. Contact AB if the

fault persists

• •

Open position key lock activated

Unlock by inserting the key

• •

Undervoltage release not energized

Check the relative supply circuit and the supply

voltage

• •

Shunt opening release remains perma-

nently energized

Check the supply circuit

Operating mechanism locked

Call Rocwell Automation

The fuse that protects the spring loading

motor protection has tripped

Replace the fuse

Faulty gearmotor for automatic spring

loading

Replace the gearmotor

Circuit-breaker closed

Press the opening pushbutton and activate the

lock

Lock in open position defective

Call AB

WARNING: If the fault or failure of the circuit-breaker in your application could cause injuries, material damage

or is highly critical, the circuit-breaker itself must be immediately removed so that it can be inspected or repaired.