Powerflex 700s - frames 5 & 6, 9frame 5 frame 6 – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual

Page 26

Advertising
background image

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

26

PowerFlex 700S - Frames 5 & 6

No. Name

Frame

Description

Wire Size Range

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Torque

Terminal
Bolt Size

(2)

(2)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Maximum

Minimum

Maximum

Recommended

1

Power Terminal Block

5
(75 HP)

(3)

(3)

Not all terminals present on all drives.

R, S, T, BR1, 2, DC+, DC-, U, V and W

50.0 mm

2

(1/0 AWG)

2.5 mm

2

(14 AWG)

See Note

(4)

(4)

Refer to the terminal block label inside the drive.

See Note

(4)

PE

50.0 mm

2

(1/0 AWG)

4.0 mm

2

(12 AWG)

5
(100 HP)

(3)

R, S, T, DC+, DC-, U, V and W

70.0 mm

2

(2/0 AWG)

16.0 mm

2

(6 AWG)

BR1, BR2

50.0 mm

2

(1/0 AWG)

2.5 mm

2

(14 AWG)

PE

50.0 mm

2

(1/0 AWG)

4.0 mm

2

(12 AWG)

6

Input power and motor connections

120.0 mm

2

(4/0 AWG)

(5)

(5)

If necessary, two wires can be used in parallel to any of these terminals using two lugs.

2.5 mm

2

(14 AWG)

6 N-m
(52 lb.-in.)

6 N-m
(52 lb.-in.)

2

SHLD Terminal

5 & 6

Terminating point for wiring shields

1.6 N-m
(14 lb.-in.)

1.6 N-m
(14 lb.-in.)

3

AUX Terminal Block

5 & 6

Auxiliary Control Voltage

(6)

PS+, PS-

(6)

External control power: UL Installation - 300V DC,

±

10%, Non UL Installation - 270-600V DC,

±

10%. Frame 1-6, 100 W

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

0.6 N-m
(5.3 lb.-in.)

0.6 N-m
(5.3 lb.-in.)

4

Fan Terminal Block
(Common Bus Only)

5 & 6

User Supplied Fan Voltage
0V AC, 120V AC, 240V AC

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

0.6 N-m
(5.3 lb.-in.)

0.6 N-m
(5.3 lb.-in.)

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

Frame 5

Frame 6

Optional

Communications

Module

L2

L1

T3

T2

T1

L3

INPUT

OUTPUT

USE 75 C

COPPER WIRE

ONLY

TORQUE
52 IN-LB

(6 N-M)

BR2

PS+

PS–

BR1

DC+

DC–

USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)

22-10
AWG

5.3 IN-LB
(0.6 N-M)

WIRE

S

TRIP

3

2

1

2

3

1

4

4

Advertising