Cable recommendations - control, Table g recommended control wire – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual

Page 34

Advertising
background image

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

34

Cable Recommendations - Control

Table G Recommended Control Wire

Type

Wire Type(s)

Description

Insulation
Rating

Digital I/O

Un-shielded

Per US NEC or applicable national or local code

300V, 60

o

C

(140

o

F),

Minimum

Shielded

Multi-conductor shielded cable such as Belden
8770(or equiv.)

0.750 mm

2

(18AWG), 3 conductor,

shielded.

Standard Analog I/O

Belden 8760/9460(or equiv.)

0.750 mm

2

(18AWG), twisted pair,

100% shield with drain

(5)

.

(5)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always

recommended.

300V,
75-90

º

C

(167-194

º

F)

Remote Pot

Belden 8770(or equiv.)

0.750 mm

2

(18AWG), 3 cond., shielded

Encoder/Pulse I/O
Less 30.5 m (100 ft.)

Combined:

Belden 9730 (or equivalent)

(1)

(1)

Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728 (or equivalent).

0.196 mm

2

(24AWG), individually

shielded.

Encoder/Pulse I/O
30.5 m (100 ft.) to 152.4 m
(500 ft.)

Signal:

Belden 9730/9728 (or equivalent)

(1)

0.196 mm

2

(24AWG), individually

shielded.

Power:

Belden 8790

(2)

(2)

Belden 8790 is 1 shielded pair.

0.750 mm

2

(18AWG)

Combined:

Belden 9892

(3)

(3)

Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm

2

(22 AWG) plus 1 shielded pair 0.5 mm

2

(20 AWG) for power.

0.330 mm

2

or 0.500 mm

2 (3)

Encoder/Pulse I/O
152.4 m (500 ft.) to 259.1 m
(850 ft.)

Signal:

Belden 9730/9728 (or equivalent)

(1)

0.196 mm

2

(24AWG), individually

shielded.

Power: Belden

8790

(2)

0.750 mm

2

(18AWG)

Combined:

Belden 9773/9774 (or equivalent)

(4)

(4)

Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774 (or equivalent).

0.750 mm

2

(18AWG), individually

shielded pair.

Stegmann Encoder

Stegmann 6-411682-xx cables with C12 FUR connections

Resolver

Paige 412081 (or equiv.) Twist, capacitance, inductance and resistance
specifications equal to or greater than cable specified

0.750 =mm

2

(18 AWG), twisted pair

300V, 80

o

C (176

o

F) minimum

SynchLink

Versalink V-System, Lucent Technologies, Specialty Fibers Technology
Division 1403-CF BLK

200/230 micron HCS (Hard Clad Silica)
650 nm (Red) Data Rate 5 Mbps

EMC Compliance

Refer to position “i” - Emission of the Catalog Number Explanation on Page 11 for details.